S-12 CITYWIDE SPRINKLER SYSTEMS, S12 sprinkler test Spring 2023. THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE QUALIFICATIONS. OWNER RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF __________ YEARS. 3 THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH REQUIREMENTS. IMPAIRMENT COORDINATOR REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. 1 SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS. 1 NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN ______ HOURS. 8 FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. OWNER OF THE BUILDING IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. 30 WHAT DOES "OOS" STAND FOR? OUT OF SERVICE OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER TAGS A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY SECTIONAL VALVES. MASTER FIRE SUPPRESSION PIPING CONTRACTOR __________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW PRESSURES BEFORE AND AFTER. DRAIN TEST RESULTS GREEN TAGS INDICATE THAT __________. NO IMPAIRMENT WAS FOUND GREEN TAGS WILL BE PLACED ON THE ____________. MAIN CONTROL VALVE SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG PLACED ON THE MAIN CONTROL VALVE. RED A _________ DISC

Meer zien Lees minder
Instelling
Vak

Voorbeeld van de inhoud

S-12 CITYWIDE SPRINKLER SYSTEMS, S12 sprinkler
test Spring 2023.
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS.
OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON
PREMISES FOR A MIN. OF __________ YEARS.
3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS.
IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE.
1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS.
1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED
TO SERVICE WITHIN ______ HOURS.
8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT.
OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT.
30
WHAT DOES "OOS" STAND FOR?
OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER
TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE
AND ANY SECTIONAL VALVES.
MASTER FIRE SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER.
DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________.
NO IMPAIRMENT WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________.
MAIN CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
____________ TAG PLACED ON THE MAIN CONTROL VALVE.
RED

, A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE.
WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE.
BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS.
INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE
THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED.
IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING.
50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR
THE ____________.
MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE
FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS.
RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS.
REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS:
REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE OPERATING
ENGINEER, AND NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS.
MASTER FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS.
30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED
WHEN SPRINKLERS ARE INSTALLED.
96
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING.
40 FAHRENHEIT
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED.
COLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING.
DRY PIPE

Geschreven voor

Vak

Documentinformatie

Geüpload op
5 mei 2023
Aantal pagina's
14
Geschreven in
2022/2023
Type
Tentamen (uitwerkingen)
Bevat
Vragen en antwoorden

Onderwerpen

$11.99
Krijg toegang tot het volledige document:

Verkeerd document? Gratis ruilen Binnen 14 dagen na aankoop en voor het downloaden kun je een ander document kiezen. Je kunt het bedrag gewoon opnieuw besteden.
Geschreven door studenten die geslaagd zijn
Direct beschikbaar na je betaling
Online lezen of als PDF

Maak kennis met de verkoper

Seller avatar
De reputatie van een verkoper is gebaseerd op het aantal documenten dat iemand tegen betaling verkocht heeft en de beoordelingen die voor die items ontvangen zijn. Er zijn drie niveau’s te onderscheiden: brons, zilver en goud. Hoe beter de reputatie, hoe meer de kwaliteit van zijn of haar werk te vertrouwen is.
ACADEMICAIDSTORE Chamberlain College Of Nursing
Volgen Je moet ingelogd zijn om studenten of vakken te kunnen volgen
Verkocht
1214
Lid sinds
4 jaar
Aantal volgers
892
Documenten
12029
Laatst verkocht
5 dagen geleden
ACADEMICAID STORE

Welcome to ACADEMICAID store! We specialize in reliable test banks, exam questions with verified answers, practice exams, study guides, and complete exam review materials to help students pass on the first try. Our uploads support Nursing programs, professional certifications, business courses, accounting classes, and college-level exams. All documents are well-organized, accurate, exam-focused, and easy to follow, making them ideal for quizzes, midterms, finals, ATI & HESI prep, NCLEX-style practice, certification exams, and last-minute reviews. If you’re looking for trusted test banks, comprehensive exam prep, and time-saving study resources, you’re in the right place.

Lees meer Lees minder
4.1

176 beoordelingen

5
98
4
29
3
28
2
6
1
15

Recent door jou bekeken

Waarom studenten kiezen voor Stuvia

Gemaakt door medestudenten, geverifieerd door reviews

Kwaliteit die je kunt vertrouwen: geschreven door studenten die slaagden en beoordeeld door anderen die dit document gebruikten.

Niet tevreden? Kies een ander document

Geen zorgen! Je kunt voor hetzelfde geld direct een ander document kiezen dat beter past bij wat je zoekt.

Betaal zoals je wilt, start meteen met leren

Geen abonnement, geen verplichtingen. Betaal zoals je gewend bent via iDeal of creditcard en download je PDF-document meteen.

Student with book image

“Gekocht, gedownload en geslaagd. Zo makkelijk kan het dus zijn.”

Alisha Student

Bezig met je bronvermelding?

Maak nauwkeurige citaten in APA, MLA en Harvard met onze gratis bronnengenerator.

Bezig met je bronvermelding?

Veelgestelde vragen