THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS.
OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON
PREMISES FOR A MIN. OF __________ YEARS.
3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS.
IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE.
1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS.
1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED
TO SERVICE WITHIN ______ HOURS.
8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT.
OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT.
30
WHAT DOES "OOS" STAND FOR?
OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER
TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE
AND ANY SECTIONAL VALVES.
MASTER FIRE SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER.
DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________.
NO IMPAIRMENT WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________.
MAIN CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
____________ TAG PLACED ON THE MAIN CONTROL VALVE.
RED
, A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE.
WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE.
BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS.
INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE
THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED.
IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING.
50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR
THE ____________.
MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE
FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS.
RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS.
REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS:
REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE OPERATING
ENGINEER, AND NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS.
MASTER FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS.
30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED
WHEN SPRINKLERS ARE INSTALLED.
96
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING.
40 FAHRENHEIT
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED.
COLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING.
DRY PIPE