S-12 CITYWIDE SPRINKLER SYSTEMS,
S12 sprinkler test- Spring 2023- 193 Q &
A.
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - -OWNER
-RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON
PREMISES FOR A MIN. OF __________ YEARS. - -3
-THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY
WITH REQUIREMENTS. - -IMPAIRMENT COORDINATOR
-REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN
________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM
SERVICE. - -1
-SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE
CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS. - -1
-NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS
RETURNED TO SERVICE WITHIN ______ HOURS. - -8
-FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER
SHALL IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE
FIRE DEPT. - -OWNER OF THE BUILDING
-IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - -30
-WHAT DOES "OOS" STAND FOR? - -OUT OF SERVICE
-OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE
DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND
CENTER - -TAGS
-A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL
VALVE AND ANY SECTIONAL VALVES. - -MASTER FIRE SUPPRESSION
PIPING CONTRACTOR
-__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC
AND FLOW PRESSURES BEFORE AND AFTER. - -DRAIN TEST RESULTS
, -GREEN TAGS INDICATE THAT __________. - -NO IMPAIRMENT WAS
FOUND
-GREEN TAGS WILL BE PLACED ON THE ____________. - -MAIN CONTROL
VALVE
-SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
____________ TAG PLACED ON THE MAIN CONTROL VALVE. - -RED
-A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS
TO INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - -WHITE
-A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS
TO INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - -BLUE
-THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________
CARRIER, CENTRAL STATION AND OCCUPANTS. - -INSURANCE
-PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL
ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE
CONDUCTED. - -IMPAIRMENT COORDINATOR
-GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT
FROM FREEZING. - -50, 40
-THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE
POSTED NEAR THE ____________. - -MAIN CONTROL VALVE
-__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE
OF THE FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3
YEARS. - -RECORDS
-FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE
COF AND COURT PROCEEDINGS. - -REVOCATION
-THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX
IF THEY HOLD THE FOLLOWING CERTS: - -REFRIGERATION
OPERATING ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND
NYS HIGH PRESSURE OPERATING ENGINEER.
-A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE
STANDPIPE AND SPRINKLER SYSTEMS. - -MASTER FIRE SUPPRESSION
PIPING CONTRACTOR (MFSPC)
, -A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS. - -30
-ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR
CONTROLLED WHEN SPRINKLERS ARE INSTALLED. - -96
-WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING. - -40 FAHRENHEIT
-__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. - -
COLD WEATHER
-________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM
CANNOT BE HEATED TO PREVENT FREEZING. - -DRY PIPE
-THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. -
-AIR PRESSURE
-IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS)
THE ALARM IS TRANSMITTED DIRECTLY TO THE _________. - -FIRE
DEPARTMENT
-DRY PIPE VALVES ARE OF A ______ DESIGN. - -CLAPPER
-DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE
NORMAL TRIP LEVEL. - -15-20
-AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME
TO ALLOW WATER INTO THE SYSTEM. - -REDUCE
-BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP
OF _______ PSI IS DETECTED IN THE SYSTEM. - -2
-IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE
SPRINKLER HEADS. - -PREACTION VALVE
-PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE _________ IS
OPENED. - -VALVE
-THREE DEVICES USED TO TRIP PREACTION VALVES ARE FIXED TEMP
DEVICES, RATE DEVICES, AND ___________ DEVICES. - -COMBINATION
-THE _________ FEATURE SHUTS OFF WATER WHEN THE FIRE IS
EXTINGUISHED AND TURNS ON AGAIN IF THE FIRE REKINDLES. - -
RECYCLING
S12 sprinkler test- Spring 2023- 193 Q &
A.
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - -OWNER
-RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON
PREMISES FOR A MIN. OF __________ YEARS. - -3
-THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY
WITH REQUIREMENTS. - -IMPAIRMENT COORDINATOR
-REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN
________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM
SERVICE. - -1
-SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE
CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS. - -1
-NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS
RETURNED TO SERVICE WITHIN ______ HOURS. - -8
-FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER
SHALL IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE
FIRE DEPT. - -OWNER OF THE BUILDING
-IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - -30
-WHAT DOES "OOS" STAND FOR? - -OUT OF SERVICE
-OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE
DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND
CENTER - -TAGS
-A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL
VALVE AND ANY SECTIONAL VALVES. - -MASTER FIRE SUPPRESSION
PIPING CONTRACTOR
-__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC
AND FLOW PRESSURES BEFORE AND AFTER. - -DRAIN TEST RESULTS
, -GREEN TAGS INDICATE THAT __________. - -NO IMPAIRMENT WAS
FOUND
-GREEN TAGS WILL BE PLACED ON THE ____________. - -MAIN CONTROL
VALVE
-SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
____________ TAG PLACED ON THE MAIN CONTROL VALVE. - -RED
-A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS
TO INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - -WHITE
-A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS
TO INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - -BLUE
-THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________
CARRIER, CENTRAL STATION AND OCCUPANTS. - -INSURANCE
-PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL
ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE
CONDUCTED. - -IMPAIRMENT COORDINATOR
-GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT
FROM FREEZING. - -50, 40
-THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE
POSTED NEAR THE ____________. - -MAIN CONTROL VALVE
-__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE
OF THE FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3
YEARS. - -RECORDS
-FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE
COF AND COURT PROCEEDINGS. - -REVOCATION
-THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX
IF THEY HOLD THE FOLLOWING CERTS: - -REFRIGERATION
OPERATING ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND
NYS HIGH PRESSURE OPERATING ENGINEER.
-A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE
STANDPIPE AND SPRINKLER SYSTEMS. - -MASTER FIRE SUPPRESSION
PIPING CONTRACTOR (MFSPC)
, -A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS. - -30
-ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR
CONTROLLED WHEN SPRINKLERS ARE INSTALLED. - -96
-WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING. - -40 FAHRENHEIT
-__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. - -
COLD WEATHER
-________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM
CANNOT BE HEATED TO PREVENT FREEZING. - -DRY PIPE
-THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. -
-AIR PRESSURE
-IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS)
THE ALARM IS TRANSMITTED DIRECTLY TO THE _________. - -FIRE
DEPARTMENT
-DRY PIPE VALVES ARE OF A ______ DESIGN. - -CLAPPER
-DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE
NORMAL TRIP LEVEL. - -15-20
-AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME
TO ALLOW WATER INTO THE SYSTEM. - -REDUCE
-BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP
OF _______ PSI IS DETECTED IN THE SYSTEM. - -2
-IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE
SPRINKLER HEADS. - -PREACTION VALVE
-PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE _________ IS
OPENED. - -VALVE
-THREE DEVICES USED TO TRIP PREACTION VALVES ARE FIXED TEMP
DEVICES, RATE DEVICES, AND ___________ DEVICES. - -COMBINATION
-THE _________ FEATURE SHUTS OFF WATER WHEN THE FIRE IS
EXTINGUISHED AND TURNS ON AGAIN IF THE FIRE REKINDLES. - -
RECYCLING