NICET LEVEL 1 EXAM 2023 WITH 100% CORRECT ANSWERS
The maximum number of 14AWG wires that can be pulled straight through a 4" X 2 1/8" square trade size metal electrical box is? 15 (NFPA 70 Table 314.16(A)) What is the first process or step you must take when working on a panel supplied with 120VAC? Lock out and Tag out the power source If power supplies are located remotely from the FACP, where shall their locations be posted? Fire alarm control panel (NFPA 72 10.6.8.2) _______ 90 degree bends are permitted in an EMT run between boxes, fittings or termination points. 4 (Max is 360 degrees) (NEC 358.26) A run of EMT shall be fastened at least every _____ feet 10 (NEC 358.30) What is the maximum rated temperature in wet locations for THHN? 75 C (NEC) The smallest single conductor size for a power limited circuit is? 18 AWG (NEC 760.142) Wiring shall be installed in accordance with NEC articles: 760, 770 and 800 (NFPA 72 12.2.4) Smoke detectors shall not be installed during construction: If permitted by the AHJ for protection during construction (NFPA 72) What reference document should be used for safe work practices with live electrical conductors? NFPA 70E NEC states that PLFA wiring used splicing must be made In listed enclosures and boxes All tools used on a construction site are to be covered under the regulations of OSHA. True