1). When using the interior metal water piping system for the grounding electrode, the
connection of the grounding electrode to the water piping system must be made ___.
Ans: (d) within the first five feet entering the building 250.2(A1)
2). 15 and 20 amp single phase 125 volt receptacles, installed on a boat-yard wharf, for general
use shall be ___.
Ans: (b) GFCI protected 555.19(B1)
3). The working clearance in front of a 2300 volt switchboard to a wooden wall is ___.
Ans: (b) 36" T. 110.34(A)
4). The terminal bar in a panelboard is connected to the neutral bar only when the panelboard
is used as ___.
Ans: (b) service euipment 250.24(A)
5). Wire terminals located in panelboards shall be arranged ___.
Ans: (d) so it will not be necessary for service personnel to reach across or beyond an
uninsulated ungrounded line bus to make connections 408.3(D)
6). The minimum allowed rating for the service disconnect of a single circuit installation is ___.
Ans: (a) 15 amps 230.79(A)
7). The service grounding electrode conductor is sized by the rating of the ___.
Ans: (d) service-entrance conductors T. 250.66
PaperStoc.com Page 1 of 6
, 8). The maximum distance that a se cablestrap can be from the meter base or service head is
___.
Ans: (b) 12" 230.51(A)
9). The code defines "unfinished basement" as portions or areas of the basement ___.
Ans: (d) limited to storage or work areas 210.8(A5)
10). The maximum size rigid metal conduit allowed for electrical construcion is ___.
Ans: (b) 6" 344.20(B)
11). Appliance outlets installed for a specific appliance shall be installed within ___ of the
intended location of the appliance.
Ans: (c) 6' 210.50(C)
12). Type nmc cable may be used in ___.
Ans: (a) dry or moist locations 334.10(B)(1)
13). Mi cable is prohibited ___
Ans: (d) where exposed to destructive corrosive conditions 332.12(2)
14). The maximum overcurrent protection for a #14 copper thhn wire installed in a raceway is
___ amperes.
Ans: (b) 15 240.2(D)(3)
15). Conductors that are paralleled, are ___.
Ans: (d) electrically joined at both ends 310.4(A)
16). Temporary wiring used on a construction project shall be removed ___.
Ans: (a) immediately upon completion of the construction 590.3(D)