spacing for smoke detectors or manufactured specs - Correct Answer rule of thumb - 30ft
manual pull station height - Correct Answer 3-1/2 to 4-1/2 ft
secondary power must turn of within ? seconds on loss of primary supply - Correct Answer
10 seconds
manual pull stations must be mounted within ? feet of exits on each floor and spaced up to
? - Correct Answer 5 ft, 200 ft
residential, secondary power supply time - Correct Answer 24 hours in normal, 4 minutes
of full alarm
commercial, secondary power supply time - Correct Answer 24 hours in normal, 5 minutes
of full alarm
live voice, secondary power supply time - Correct Answer 24 hours in normal, 15 minutes
of full power
audible device decibels, public - Correct Answer 75 db minimum or 15 above ambient
audible device decibels, private - Correct Answer 45 db or 15 db above ambient
smoke detector test frequency, functionality - Correct Answer annually
smoke detector test frequency, visual - Correct Answer semi-annually
smoke detector test frequency, sensitivity - Correct Answer at installation and every
alternate year thereafter
smoke detectors, CAN or CANNOT, be supported by their circuit conductors - Correct
Answer cannot
acceptable to the AHJ (authority having jurisdiction) - Correct Answer Approved
alert tone, ? ,a live voice instruction - Correct Answer precedes
protective covers for manual pull stations must be ? and cannot be made on site - Correct
Answer listed
mirrors or reflectors can be used on what type of smoke detectors - Correct Answer
projected beam detectors