In systems where the sole water supply is through a backflow preventer and/ or
pressure reducing valves, the main drain test of at least one system downstream
of the device shall be conducted ________? - ANSWERS-Quarterly
Hose connections should be inspected, tested, and maintained in accordance with
NFPA 25 Chapter ______ and Chapter____? - ANSWERS-6,13
When is the proper time for the employee's to receive training on the company
fall arrest system? - ANSWERS-Before using the fall arrest system
What is a fire service main? - ANSWERS-A pipe and its appurtenances on private
property/ Pipe between a source of water and the base of the system riser
, Name the system that utilizes a plate through which a passes a specific amount of
foam concentrate at a specific pressure. - ANSWERS-Orifice Plate Proportioning
During an inspection, which of the following would be identified as a sprinkler
which shall be replaced? - ANSWERS-Corrosion
What are the inspection requirements for hangers and seismic braces installed in
concealed spaces? - ANSWERS-Periodic inspection is not required
Gauges shall be replaced every _____ or tested every _____ by comparison with a
calibrated gauge - ANSWERS-5 years/ 5 years
Where air pressure supervision is connected to a constantly attended location
gauges shall be inspected ______? - ANSWERS-Monthly
What is a purpose of a control valve - ANSWERS-Control Flow to water based fire
protection system
The gauge on the quick opening device shall indicate _____ as compared to the
gauge on the system side of the dry pipe valve? - ANSWERS-the same pressure
What type of test shall be provided when a valve is returned to service to
determine that the valve is open? - ANSWERS-Valve status test