MASSACHUSETTS OIL BURNER EXAM WITH (Q&A) 2024//25 If the oil level in the tank is 4 feet below the fuel unit in 10 feet away, the approximate vacuum should be - CORRECT ANSWER 5 - 6 inches If the operating vacuum reading a significantly above the calculated vacuum, you probably have a - CORRECT ANSWER Clogged oil filter If the operating vacuum reading is significantly less than the calculated vacuum, you probably have a - CORRECT ANSWER Suction line leak It is best to connect your unit as a one pipe system instead of a 2 pipe system because - CORRECT ANSWER One pipe leads to longer filter life and eliminates worries about leaking return lines A fuel de-aerator : - CORRECT ANSWER Eliminates the need for a return line back to the tank A cause of pulsating oil pump pressure and a pulsating fire is - CORRECT ANSWER Air leaks in the suction line Increasing the fuel pump pressure will - CORRECT ANSWER Increase the flow rate The purpose of an oil burner nozzle is to - CORRECT ANSWER Atomize the oil, provide a pattern of oil spray, and meter the amount of oil burned When replacing nozzle - CORRECT ANSWER Follow the manufacturer's recommendations To reduce combustion problems caused by cold oil - CORRECT ANSWER Increase the pump pressure, install a nozzle line pre-heater, and use additives or kerosene to lower viscosity Nozzle after trip can be caused by - CORRECT ANSWER a defective pressure regulating valve, air in the nozzle line, and oil expansion in the nozzle after shut down

Meer zien Lees minder
Instelling
MASSACHUSETTS OIL BURNER
Vak
MASSACHUSETTS OIL BURNER

Voorbeeld van de inhoud

MASSACHUSETTS OIL BURNER EXAM WITH
(Q&A) 2024//25

If the oil level in the tank is 4 feet below the fuel unit in 10 feet away, the approximate
vacuum should be
- CORRECT ANSWER 5 - 6 inches

If the operating vacuum reading a significantly above the calculated vacuum, you
probably have a
- CORRECT ANSWER Clogged oil filter

If the operating vacuum reading is significantly less than the calculated vacuum, you
probably have a
- CORRECT ANSWER Suction line leak

It is best to connect your unit as a one pipe system instead of a 2 pipe system because
- CORRECT ANSWER One pipe leads to longer filter life and eliminates worries about
leaking return lines

A fuel de-aerator
: - CORRECT ANSWER Eliminates the need for a return line back to the tank

A cause of pulsating oil pump pressure and a pulsating fire is - CORRECT ANSWER Air
leaks in the suction line

Increasing the fuel pump pressure will
- CORRECT ANSWER Increase the flow rate

The purpose of an oil burner nozzle is to
- CORRECT ANSWER Atomize the oil, provide a pattern of oil spray, and meter the
amount of oil burned

When replacing nozzle
- CORRECT ANSWER Follow the manufacturer's recommendations

To reduce combustion problems caused by cold oil
- CORRECT ANSWER Increase the pump pressure, install a nozzle line pre-heater,
and use additives or kerosene to lower viscosity

Nozzle after trip can be caused by
- CORRECT ANSWER a defective pressure regulating valve, air in the nozzle line, and
oil expansion in the nozzle after shut down

, The flow rate stamped on the nozzle is based on:
- CORRECT ANSWER 100 PSI

A proper combustion chamber:
- CORRECT ANSWER Is large enough so the fire doesn't touch (impinge on) any
surface, reflects heat back into the fire, and is made of material (like ceramic) that heats
up quickly and cools off quickly

Too much draft over the fire can occur when
- CORRECT ANSWER There are leaks between the sections of the boiler that let
basement air into the heat exchanger
The cross connection between two supply tanks shall not exceed?
- CORRECT ANSWER 660 gallons

When is an automatic draft control not required?
- CORRECT ANSWER When the equipment is designed to control the draft.

Combustion performance testing can indicate:
- CORRECT ANSWER Improper air oil mixture, too much combustion air, and low pump
pressure.

If a second oil-burning appliance is installed in a single chimney, you must insure:
- CORRECT ANSWER Sufficient draft is available for safe operation of all connected
equipment.

Delayed ignition can be caused by:
- CORRECT ANSWER Weak ignition transformer

You should replace the oil burner nozzle with:
- CORRECT ANSWER The manufacturers recommended nozzle spray pattern and
spray angle.

Viscosity problems can be corrected by:
- CORRECT ANSWER Decreasing the nozzle size and increasing the pump pressure
accordingly

The minimum operating pressure of an oil pump is:
- CORRECT ANSWER 100 PSI

If a stack relay fails you, must?
- CORRECT ANSWER Replace it with an approved type controller

Aqua stats are normally found on what type of heating systems?
- CORRECT ANSWER Hydronic

Geschreven voor

Instelling
MASSACHUSETTS OIL BURNER
Vak
MASSACHUSETTS OIL BURNER

Documentinformatie

Geüpload op
10 november 2024
Aantal pagina's
5
Geschreven in
2024/2025
Type
Tentamen (uitwerkingen)
Bevat
Vragen en antwoorden

Onderwerpen

$18.49
Krijg toegang tot het volledige document:

Verkeerd document? Gratis ruilen Binnen 14 dagen na aankoop en voor het downloaden kun je een ander document kiezen. Je kunt het bedrag gewoon opnieuw besteden.
Geschreven door studenten die geslaagd zijn
Direct beschikbaar na je betaling
Online lezen of als PDF

Maak kennis met de verkoper
Seller avatar
janetheuri
3.0
(1)

Maak kennis met de verkoper

Seller avatar
janetheuri Teachme2-tutor
Volgen Je moet ingelogd zijn om studenten of vakken te kunnen volgen
Verkocht
7
Lid sinds
1 jaar
Aantal volgers
0
Documenten
517
Laatst verkocht
10 maanden geleden

3.0

1 beoordelingen

5
0
4
0
3
1
2
0
1
0

Waarom studenten kiezen voor Stuvia

Gemaakt door medestudenten, geverifieerd door reviews

Kwaliteit die je kunt vertrouwen: geschreven door studenten die slaagden en beoordeeld door anderen die dit document gebruikten.

Niet tevreden? Kies een ander document

Geen zorgen! Je kunt voor hetzelfde geld direct een ander document kiezen dat beter past bij wat je zoekt.

Betaal zoals je wilt, start meteen met leren

Geen abonnement, geen verplichtingen. Betaal zoals je gewend bent via iDeal of creditcard en download je PDF-document meteen.

Student with book image

“Gekocht, gedownload en geslaagd. Zo makkelijk kan het dus zijn.”

Alisha Student

Bezig met je bronvermelding?

Maak nauwkeurige citaten in APA, MLA en Harvard met onze gratis bronnengenerator.

Bezig met je bronvermelding?

Veelgestelde vragen