Tank with liquid filled annular or that has vacuum on it at the tine of delivery do
not require a provided manufacturer pre-installation procedures are followed
A. True
B. False
A. True
A safety harness must be worn when working in a confined space
A. True
B. False
A. True
A typical type of leak detection for suction piping is
A. Under-pump check valve
B. Electronic line leak detection
C. Automatic tank gauge (ATG)
A. Under-pump check valve
A typical type of release detection equipment for pressurized piping is
A. Electronic line leak detectors
,B. Mechanical line leak detectors
C. Interstitial monitoring
D. All of the above
D. All of the above
A UST system can be temporarily closed for___months. After this time period the
tanks must be removed or put back into service
A. 12 months
B. 36 months
C. 48 months
A. 12 months
After backfill is placed to the level of the top of the tank, it is recommended that
the tank be ballasted with product or water
A. True
B. False
A. True
All methods of tank anchoring use the weight of the backfill and paving on top of
the tank to offset the buoyancy forces
A. True
B. False
, A. True
All UST systems equipped with cathodic protection systems must have the system
inspected within___months of installation and every___years thereafter by a
qualified cathodic protection tester
A. 1 month / 1 year
B. 6 month / 3 year
C. 1 year / 5 year
B. 6 month / 3 year
An acceptable form of cathodic protection system is
A. Impressed current
B. Sacrificial anode
C. Spray paint
D. Both A and B
D. Both A and B
An efficient piping layout minimizes the length of piping, enhances operations,
and facilities testing and services
A. True
B. False
A. True