Assessment Questions with Answers
Which of the following is not considered hanging hardware?
nozzle, swivel, whip hose, shear valve - correct answer shear valve
Per EO. VR-201-E, the dispenser must be removed from service if the dispensing
vacuum of the Healy VP-1000 pump is below how many inches of water column? -
correct answer 60
In a coaxial hose for a balance system, the product flows through the? - correct
answer inner hose
Per the Vapor Recovery Equipment Defects List (VRED), the _________ of any
component required to be used by the system's EO is not considered a defect. -
correct answer disconnection
The three elements in a fire triangle are? - correct answer fuel, oxygen & ignition
source
According to PEI RP-300, a combustible gas indicator is used to ? - correct answer
detect vapor leaks in the vapor recovery system
Per CP-201, liquid traps in the dispenser vapor piping are: - correct answer not
allowed
Which of the following is not an overfill device ?
ball-float, tank overfill alarm, spill-bucket, drop-tube flapper valve - correct answer
spill-bucket
Piping should have a minimum and maximum slope of ______ inch - correct
answer l/8"-1/4"
What is the appropriate way to clean up a small spill of gasoline? - correct answer
apply absorbent to the affected area, then remove & dispose of absorbent in
accordance with applicable requirements
Placing a bare copper wire from the __________ to the _________with it's ends
exposed is helpful with pipe run locating. - correct answer Dispenser pipe run to the
Tank Turbine
, One of the approved methods for overfill prevention is to have an overfill device that
will automatically shut off fill into the tank when the tank is a maximum of _____
percent full. - correct answer 95%
In the PEI 300 manual, pressure decay, dynamic back pressure and A/L testing
satisfy who's testing requirements? - correct answer CARB
When removing liquid from a sump or spill bucket and the liquid contains fuel, it must
_________ - correct answer be managed as hazardous waste
Before working on any electrical circuits always de-energize and use _____ rules. -
correct answer NFPA
The two point Phase I vapor recovery system requires that a separate vapor
recovery riser pipe be installed in the tank and be equipped with a _____ ? - correct
answer vapor recovery adaptor
The term hanging hardware refers to? - correct answer nozzle-hose-breakaway
A valve installed in a motor-vehicle fueling hose designed to separate with little or no
product spillage when excessive pulling force is placed on the hose is called a
____________ - correct answer breakaway
In the PEI# 500 manual, a Level II Qualified Person can do all EXCEPT: open
cabinet doors, reconnect breakaways, measure flow rates, repair or replace
dispenser components - correct answer repair or replace dispenser components
A Gilbarco Vapor- Vac, OPW Vapor Saver system is considered to have a vapor
recovery equipment defect (VERD) if the vapor escape guard on an OPW 12-VW
nozzle is missing or damaged on at least ___% of the circumference of the device? -
correct answer 75
Typically, vapor return piping is connected to: - correct answer the lowest grade
gasoline tank
CARB's most recent vapor recovery regulations are known as: - correct answer
EVR (enhanced vapor recovery)
A liquid collection point is installed in: - correct answer the vapor return piping
The connection of vent risers aboveground to form a single vent opening is called a
_______________ - correct answer manifold
When installing a Healy# VP-1000 Vac-Motor the technician should do all EXCEPT:
replace the nozzle, wear eye protection, properly barricade the area, turn off power
to the dispenser - correct answer replace the nozzle