Questions and Answers
1. I do a ____ after replacing a spout to a Healy 900 nozzle - Correct Answer shut off
test
2. In a balance hose the gasoline flows in - Correct Answer Inner hose
3. After the installation of the vapor piping and before back filling, PEI 300 suggests
some methods to document piping layout, except? - Correct Answer Drawing with a
pen, pipe layout on the cover of the tank manual.
4. During VO-1000 you don't - Correct Answer Work without eye protection
5. An Overfill Alarm device needs to be located - Correct Answer Where it can be
heard or seen by the delivery location.
6. When in a GDF you can avoid the installation of UDC? - Correct Answer No
exceptions of any GDF.
7. What is considered an Underground Storage Tank? - Correct Answer Tank and
piping only
8. Gasoline vapors are 3/4 times _____ than air - Correct Answer Heavier
9. Compounds with a high vapor pressure such as gasoline will evaporate readily and
will typically - Correct Answer Have a low Flashpoint.
10. The ____ is the valve that controls pressure and vacuum on the tank. - Correct
Answer P/V Valve
11. The vapor piping must be all, but not - Correct Answer Compatible with
underground environment.
12. The Shear Valve is installed ____ - Correct Answer At the base of the dispenser.
13. What is the max length of a Healy Hose Phase 2? - Correct Answer 20 Feet.
14 A ___ is a component of the hanging hardware that separates when it's applied a
force? - Correct Answer Breakaway.
, 15. UL listed means all except : - Correct Answer Worldwide Approved.
16. After a drive off, a technician should not - Correct Answer Ask attendant to fill out a
drive off accident report.
17. The executive order 201-A says that the reconnection of the breakaway needs to be
- Correct Answer Logged in the maintenance GDF.
18. What is not a secondary containment testing method? - Correct Answer Statistical
Inventory Reconciliation.
19. The air clean separator must be located in the GDF - Correct Answer No more
than 100 ft from the vent riser.
20. The PEI-500 recommends that to avoid being shocked by electricity or soaked with
gasoline that? - Correct Answer You must disconnect power to all electric devices.
21. Which of these refer to a vapor recovery stage 1? - Correct Answer Delivery of
gasoline and UST.
22. Which is not part of the hanging hardware? - Correct Answer Shear Valve
23. What is not a part of a stage 2 vapor recovery? - Correct Answer Monitoring
equipment
24. To install a Healy Z083B Vapor Vac Kit you need the following tools except -
Correct Answer Stretching copper tool
25. After July 1 2004 continuous monitoring on secondary containment is required on? -
Correct Answer Tanks, sumps, UDC where single wall pipe is present.
26. The 1/8 inch of foot slope in vapor piping may not be applied if? - Correct Answer
Should always apply to avoid blocks.
27. What is the minimum nominal internal diameter for a vapor riser stage 2? - Correct
Answer 1"
28. What should you do in case of a large spill and you are waiting for the emergency
response? - Correct Answer Try to clean and contain the spill as much as possible.
29. A secondary containment on vent lines is not required if? - Correct Answer A ball
float will stop delivery at 90% tank capacity.
30. You need to install a secondary containment if
A. You replace underground pipe
B. For new installation after July 2 2004 - Correct Answer Both A and B.