ICC CALIFORNIA UST SERVICE TECHNICIAN QUESTIONS AND ANSWERS A+ GRADED .Buy Quality Materials! UDC was required at time of installation for all systems installed after? January 1, 2000 July 1, 2005, service techs shall possess or work under someone who has a current certification indicating he or she has passed the? ICC UST Service Technician Exam ICC cert must be renewed every? 24 months Service techs must possess or be employed by a person who has the appropriate contractor's license unless? The individual has a tank testing license Service tech is defined by any individual who? Tests UST monitoring equipment, trouble shoots UST systems, and/or installs UST monitoring equipment. If the manufacturer training no longer exist, the local agency may? Approve comparable alternate training . UST includes? Tank and connected piping What is considered a UST? A petroleum storage tank. What UST system meets the requirements for secondary containment? Doubled wall tanks According to title 23; the following piping components if installed after July 1, 1987 must have secondary containment. Pressured product piping Considered "pipe" on tanks installed after July 1, 2003. Pressured product piping and below ground vapor recovery. Under dispenser containment (UDC) was required for all existing UST systems by December 31, 2003 System for exchanging gas vapors in a storage tank and product in a fuel delivery truck Stage 1 vapor recovery An approved method for non-visual monitoring for existing UST systems. Statistical Inventory Reconciliation (SIR) ATG must be capable for detecting a release of? 0.2 gallons per hour What is no longer an approved method for non-visual monitoring on existing UST systems? Manual inventory reconciliation. Automatic line leak detectors installed on underground piping with secondary containment shall be capable of detecting a leak of ? 3 gallons per hour at 10 psi How often should ATG be programmed to test the tank? At least monthly According to PEI RP 300, a combustible gas can be used to? Detect vapor leaks in a vapor recovery system. According to PEI RP 300, a written scope of work for vapor recovery installation should include? Construction plans Positive shut off overfill protection device must stop the flow of fuel when the tank is no more then? 95% full According to Executive Order (EO) VR 201-A , what could cause a nozzle shut off mechanism or malfunction? Depended filter seal damage According to VR 201-A, breakaway reconnection must be? Logged in GDF log According to PEI RP 300 what is an INCORRECT method of documenting piping location? Sketching a diagram on the inside cover of vapor recovery equipment manual According to PEI RP 300 as built drawing or pictures of the underground pipping and other components shall be_________. maintained as long as UST is in service. According to EO VR 101-E maintenance records are required to include what? Name and Designated UST Operator. The Phil-Tite EVR Phase 1 system require that vapor vent pipes at any UST system be Used with no more than 3 p/v valves According to EO VR 2010 after installing a new spout assembly in the Healy 900 nozzle the following test must be conducted? Nozzle dispensing shut off test According to Healy EO VR 201-A a vapor recovery record is to be maintained by? Gasoline dispensing facility operator(GDF) An enhanced leak detection test is required within how many feet of a public drinking well? 1000 feet What are the components of the Fire Triangle? Fuel, Heat/Ignition Source, Oxygen If equipped with an over fill alarm, it must be located? So it can be seen or heard from the delivery location. If installed, the following requires independent 3rd party certification to prove compliance with established regulations. Automatic Tank Gauge, Liquid Product Detectors, SIR Where are ATG's installed? Opening in top of the tank What is true about ATG's They're capable of alarming operator of low product level

Show more Read less
Institution
Course

Content preview

ICC CALIFORNIA UST SERVICE TECHNICIAN QUESTIONS
AND ANSWERS A+ GRADED .Buy Quality Materials!

UDC was required at time of installation for all systems installed after?
January 1, 2000
July 1, 2005, service techs shall possess or work under someone who has a
current certification indicating he or she has passed the?
ICC UST Service Technician Exam
ICC cert must be renewed every?
24 months
Service techs must possess or be employed by a person who has the appropriate
contractor's license unless?
The individual has a tank testing license
Service tech is defined by any individual who?
Tests UST monitoring equipment, trouble shoots UST systems, and/or installs UST
monitoring equipment.
If the manufacturer training no longer exist, the local agency may?
Approve comparable alternate training .
UST includes?
Tank and connected piping
What is considered a UST?
A petroleum storage tank.
What UST system meets the requirements for secondary containment?
Doubled wall tanks
According to title 23; the following piping components if installed after July 1,
1987 must have secondary containment.
Pressured product piping
Considered "pipe" on tanks installed after July 1, 2003.
Pressured product piping and below ground vapor recovery.
Under dispenser containment (UDC) was required for all existing UST systems by
December 31, 2003
System for exchanging gas vapors in a storage tank and product in a fuel delivery
truck
Stage 1 vapor recovery
An approved method for non-visual monitoring for existing UST systems.
Statistical Inventory Reconciliation (SIR)
ATG must be capable for detecting a release of?
0.2 gallons per hour
What is no longer an approved method for non-visual monitoring on existing UST
systems?
Manual inventory reconciliation.
Automatic line leak detectors installed on underground piping with secondary
containment shall be capable of detecting a leak of ?

,3 gallons per hour at 10 psi
How often should ATG be programmed to test the tank?
At least monthly
According to PEI RP 300, a combustible gas can be used to?
Detect vapor leaks in a vapor recovery system.
According to PEI RP 300, a written scope of work for vapor recovery installation
should include?
Construction plans
Positive shut off overfill protection device must stop the flow of fuel when the
tank is no more then?
95% full
According to Executive Order (EO) VR 201-A , what could cause a nozzle shut off
mechanism or malfunction?
Depended filter seal damage
According to VR 201-A, breakaway reconnection must be?
Logged in GDF log
According to PEI RP 300 what is an INCORRECT method of documenting piping
location?
Sketching a diagram on the inside cover of vapor recovery equipment manual
According to PEI RP 300 as built drawing or pictures of the underground pipping
and other components shall be_________.
maintained as long as UST is in service.
According to EO VR 101-E maintenance records are required to include what?
Name and Designated UST Operator.
The Phil-Tite EVR Phase 1 system require that vapor vent pipes at any UST
system be
Used with no more than 3 p/v valves
According to EO VR 2010 after installing a new spout assembly in the Healy 900
nozzle the following test must be conducted?
Nozzle dispensing shut off test
According to Healy EO VR 201-A a vapor recovery record is to be maintained by?
Gasoline dispensing facility operator(GDF)
An enhanced leak detection test is required within how many feet of a public
drinking well?
1000 feet
What are the components of the Fire Triangle?
Fuel, Heat/Ignition Source, Oxygen
If equipped with an over fill alarm, it must be located?
So it can be seen or heard from the delivery location.
If installed, the following requires independent 3rd party certification to prove
compliance with established regulations.
Automatic Tank Gauge, Liquid Product Detectors, SIR
Where are ATG's installed?
Opening in top of the tank
What is true about ATG's
They're capable of alarming operator of low product level

, The following types of releases must be reported to the local agency.
Releases greater than 25 gallons that escape secondary containment. Release that
escape primary containment. Releases less than 25 gallons which escape secondary
containment
If an unauthorized product release meets the requirements for reporting to the
local agency, verbal notification must be made within ____hours, followed by a
written notification within ____days.
24 HRS, 5 DAYS
The following unusual conditions shall be reported to the local agency, EXCEPT:
Water in spill buckets
If the monitoring system detects a leak that has occurred, the local agency must
be notified unless______.
Unless the monitoring device is found to be defective and is immediately repaired.
The written report submitted to the local agency after an unauthorized release is
required to include the following EXCEPT:
Cause of release
An unauthorized release which does not escape secondary containment, requires
only recordation on the Operators Manual Report provided if what criteria is met?
It did not cause deterioration of secondary containment. It did not increase the hazard of
fire. It was cleaned up within eight hours and it was cleaned up within eight hours
detection.
Recording of an authorized release in the operators monitoring records shall
include?
Actions taken to prevent further releases.
If a authorized release meets reporting requirements of Title 23, section 2652, the
report must be filed within the? (Un or A?)
Local agency
Which statement concerning the annual monitor certification is most correct?
Local agencies must be notified 48 hours prior to certification in results must be
submitted within 30 days of certification.
The annual monitor certification may be performed by?
A person possessing the appropriate contractor's license. An individual trained and
certified by the manufacture of the monitoring equipment.
The following is true of secondary containment EXCEPT:
Must be tested every 24 months.
Enhanced the detections results must be submitted to ___ within ___days
the local agency and state water resources control board within 60 days.
The EPA recommends that monthly the operator should conduct a walk-through
inspection of the following EXCEPT: the operator should conduct a monthly walk-
through inspection... or is this a DO walk thorough?- the monthly DO should
conduct a walk-through inspection...
Facility lighting
Cathodic protection systems must be tested within ____months of installation
and every ____months thereafter.
tested within 6 months of installation and every 36 months thereafter.

Written for

Course

Document information

Uploaded on
November 17, 2024
Number of pages
18
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

$10.49
Get access to the full document:

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF


Also available in package deal

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
TopGradeSolutions Chamberlain College Of Nursing
Follow You need to be logged in order to follow users or courses
Sold
97
Member since
2 year
Number of followers
9
Documents
13303
Last sold
11 hours ago
TOPGRADESOLUTIONS

Here we offer revised study materials to elevate your educational outcomes. We have verified learning materials (Research, Exams Questions and answers, Assignments, notes etc) for different courses guaranteed to boost your academic results. We are dedicated to offering you the best services and you are encouraged to inquire further assistance from our end if need be. Having a wide knowledge in Nursing, trust us to take care of your Academic materials and your remaining duty will just be to Excel. Remember to give us a review, it is key for us to understand our clients satisfaction. We highly appreciate clients who always come back for more of the study content we offer, you are extremely valued. All the best.

Read more Read less
4.9

171 reviews

5
159
4
7
3
4
2
0
1
1

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions