And Answers Rated A+
, Electrical Journeyman Test 2024 With Complete Questions
And Answers Rated A+
A fixed light will be allowed to be 30 amp provided the socket is rated duty.
a. Light
b. Medium
c. Heavy
d. Extra Heavy ✔✔c. Heavy
From the Skilled Trades Act, Section 7 "Except as otherwise provided in this article or in
subsection (3), and individual other than an individual who is licensed under this article
and working under the direction of a holder of an electrical contractors
licence, shall not in any manner undertake to execute any electrical work". ✔✔...And
employed by and...
A box with (2) 14/3 NM, one yoke, and a clamp requires a minimum or cubic
inches.
a. 16
b. 18
c. 20
d. 22 ✔✔c. 20
NM Cable in a 2x4x2.5 plastic box will not require a cable clamp if secured within
inches of the box.
a. 8
b. 12
c. 16
d. 20 ✔✔a. 8
A box with #10 AWG THHN will require a free space of inches.
a. 2
b. 2.25
c. 2.5
d. 3 ✔✔c. 2.5 (See Table 314.16 (B).)
A mobile home with 100 amp service will require service conductors of AWG.
a. #4
b. #3
c. #2
d. #1 ✔✔a. #4 (See 550.33 (B) and 310.15 (B)(7).)
A service with (4) 4" PVC conduits with (4) 800KCMIL feeder in each will require a main
bonding jumper of what AWG?
a. 4/0
b. 1/0