Who is responsible for the inspection, testing, maintenance and impairment of a
water based fire protection system? - ANSWER-The Property owner or designated
representative
Who's responsibility is it to provide accessibility to components of a water based
fire protection system? - ANSWER-The property owner or designated
representative
Who shall correct or repair deficiencies or impairments found during the
inspection, test and maintenance required by standard? - ANSWER-The property
owner or designated representative
Who is qualified to preform the corrections and repairs of a water based fire
protection system? - ANSWER-Qualified maintenance personal or a qualified
contractor
A permanently marked metal or rigid plastic information sign shall be placed at the
system control riser supplying an antifreeze loop, dry system, preaction, or
auxiliary system control valve? - ANSWER-An Information Sign,
Records made during all inspections, tests and maintenance shall be made
available to who upon request? - ANSWER-The Authority Having Jurisdiction
All records shall be maintained by? - ANSWER-The Property Owner
, How long should subsequent records be retained? - ANSWER-1 year,
After the testing and reinstallation of plugs and caps for auxiliary drain and test
valves, what action is required? - ANSWER-Shall be restored to full operational
condition,
To avoid false alarms where a supervisory service is provided the alarm receiving
facility shall be notified by the property owner or designated representative before?
- ANSWER-conducting any test or procedure that could result in the activation of
an alarm,
Sprinklers shall be inspected when and how? - ANSWER-Shall be inspected from
the floor level annually
Sprinklers shall not show signs of the following? - ANSWER-leakage; shall be
free of corrosion, foreign materials, paint, and physical damage; and shall be
installed in the correct orientation
Sprinklers installed installed in concealed spaces such as above ceilings shall
what? - ANSWER-Shall not require inspection,
Sprinklers installed in areas that are inaccessible for safety considerations due to
process operations shall be inspected? - ANSWER-During each scheduled
shutdown
The supply of spare sprinklers shall be inspected when? - ANSWER-Annually,