26401 EVITP: Load and Feeder Calculations Exam Questions with 100% Correct Answers | Latest Version 2025 | Verified
What is the minimum demand required for the portion of a feeder that supplies 30ft of show window? 30ft x 200va = 6000 va Residential Small apliance circuits must be rated at __________ per NEC 220.52(A) 1500 va When performing load calculations for farm buildings the load that must be included in the calculation at 100% demand must be at least _______ . 60 amps The demand lighting load for a 20,000 square foot motel with no dining room or ballroom is ____ per NEC 220.12 and 220.42 18,000 va What is the demand lighting load for a 100,000 square foot hotel with no dining room or ballroom is ____ per 220.12 and 220.42 ? 72,000 va When calculating the feeder load for a motor Control Center supplying several Motors per 430.24 you must ______ . Determine the sum of all the motor loads plus 25% of the largest motor. A commercial kitchen with six or more pieces of kitchen equipment is subject to a demand factor of ___________ per NEC table 220.56. 65% demand factor What is a tap conductor? When the overcurrent protection for a conductor is located on the load side rather than the supply side of a