ACTUAL EXAM COMPLETE 250 QUESTIONS AND
CORRECT DETAILED ANSWERS (VERIFIED
ANSWERS) |ALREADY GRADED A+||BRAND
NEW!!
According to California Law, UST systems installed after July 1, 2003,
require a one-time ELD test to ensure that the tank is product tight...
a.) If the tank is located within one (1) mile of a public drinking water
well
b.) If the tank is located within 1000 feet of a public drinking water well
c.) Unless the tank is equipped with secondary containment
d.) In all cases - ANSWER--For ALL tanks before use (H&SC 25290.2 (I))
d.) In all cases
H&SC, Sec 25290.2(i)
The written report submitted to the local agency after an unauthorized
release is required to include the following except:
a.) Description of actions taken to stop the release
b.) Cause of the release
c.) Method of disposal of released product
, ICC U2 UST DECOMMISSIONING NEWEST 2025
ACTUAL EXAM COMPLETE 250 QUESTIONS AND
CORRECT DETAILED ANSWERS (VERIFIED
ANSWERS) |ALREADY GRADED A+||BRAND
NEW!!
d.) Date on which the release was discovered - ANSWER--b.) Cause of
the release
CCR Title 23, Sec 2652(c)
An unauthorized release which does not escape from secondary
containment only requires a record on the operator's monitoring
reports provided:
A. It did not increase the hazard of fire
B. It did not cause any deterioration of the secondary containment
C. It was cleaned up within 8 hours of detection
D. All of the above - ANSWER--D. All of the above
H&SC, Sec 25294
The annual monitoring certification may be performed by:
A. A person possessing the appropriate contractors licenses
, ICC U2 UST DECOMMISSIONING NEWEST 2025
ACTUAL EXAM COMPLETE 250 QUESTIONS AND
CORRECT DETAILED ANSWERS (VERIFIED
ANSWERS) |ALREADY GRADED A+||BRAND
NEW!!
B. An individual trained and certified by the manufacturer of the
monitoring equipment
C. A designated UST operator
D. A person who meets the requirements of both a and b - ANSWER--
D. A person who meets the requirements of both a and b
CCR Title 23, Sec 2715(i)
The following is true of secondary containment testing, EXCEPT:
a.) Must be tested every 24 months
b.) Must be tested every 36 months
c.) Results must be submitted to the local agency within 30 days of
testing
d.) Local agency must be notified 48 hours prior to testing - ANSWER--
a.) Must be tested every 24 months
CCR Title 23, Sec 2637(a)
, ICC U2 UST DECOMMISSIONING NEWEST 2025
ACTUAL EXAM COMPLETE 250 QUESTIONS AND
CORRECT DETAILED ANSWERS (VERIFIED
ANSWERS) |ALREADY GRADED A+||BRAND
NEW!!
Records of cathodic protection system maintenance must be kept on
file for ______________.
a.) 10 years
b.) 1.5 years
c.) 3 years
d.) 6.5 years - ANSWER--d.) 6.5 years
CCR Title 23, Sec 2712(b)
Impressed current cathodic protection systems shall be inspected no
less than every ___________ to ensure that they are in proper working
order:
a.) 60 days
b.) 90 days
c.) 30 days
d.) 120 days - ANSWER--a.) 60 days