Terms in this set (138)
Installers of a category 1 6010
Medical gas pipe
distribution system must
be qualified in
accordance with ASSE
6010. What is certification
requirement for installers
of Category
3 Medical gas pipe
distribution system?
When is the initial After blowdown of the distribution piping
pressure test conducted
by the installer?
In those portions of Polymeric
systems intended to
handle oxygen pressures
greater than 350 PSI, the
interconnecting hose
shall not contain ____
materials.
https://quizlet.com/1022647544/medical-gas-practice-test-2-2025-updatecomprehensive-questions-and-verified-answers-complete-solutions-ass… 1/24
,3/25/25, 12:48 PM Medical Gas Practice Test 2 2025 update|comprehensive questions and verified answers (complete solutions) ASSURED SU…
Which of these is an Color coding
NFPA 99 requirement for
the labeling of pipes in a
medical gas system.
A wireless The device shall be supervised such that failure
communication device is communication shall initiate an alarm.
employed in a medical
gas or vacuum warning
system. Which type of
supervision is required
for this device?
Wat sort of treatment is The cut ends may be rolled smooth or deburred
permited before brazing
the cut ends of a tube to
be installed
in medical gas piping
system
Manifolds for gas Local signal to master alarm panel
cylinders shall actuate a
____
signal and shall activate
an indicator
at all _____ alarm panels to
indicate when, or just
before, changeover from
one header
to the other.
Where liquid ring Local
compressors are used, air
receivers shall be
equipped with a high
water level sensor that
activates a ______
alarm indicator.
https://quizlet.com/1022647544/medical-gas-practice-test-2-2025-updatecomprehensive-questions-and-verified-answers-complete-solutions-ass… 2/24
, 3/25/25, 12:48 PM Medical Gas Practice Test 2 2025 update|comprehensive questions and verified answers (complete solutions) ASSURED SU…
Instrument air systems -22 degrees
shall activate the alarm
systems when the dew
point at system pressure
exceeds how many
degrees Fahrenheit
In a non-anesthetizing Station Outlet / Inlet
area, on which side of the
zone valve shall the
pressure / vacuum sensor
be located?
What is the purpose of To assure that all ambient air has been removed
using an oxygen analyzer from the pipeline
in the pipeline purge
prior to brazing?
Performance 6 months
qualifications of Braziers
shall remain in effect
indefinitely unless the
Brazier does not raise
with the qualifying
procedure for longer
than what time period.
Pipe labels should be 20 ft
located at a maximum
interval at how many
feet?
The installation of ASME section IX
medical gas and vacuum
systems, including
brazing, shall be made
by experienced, qualified
and competent installers.
Installers shall be
certified to the
requirements which
codes/standards?
https://quizlet.com/1022647544/medical-gas-practice-test-2-2025-updatecomprehensive-questions-and-verified-answers-complete-solutions-ass… 3/24