NICET
NICET LEVEL 2 FIRE ALARMS (2024/ 2025 U PDA
M M M M M M M
TE) QS & AS| 100% CORRECT| G RADE A (VERIFIED
M M M M M M M M
ANSWERS) M
Whenmascendingmormdescendingm ammetalmladder,mthemclimberm mustm __________
____
A.mcountmthemsteps
B.mlookmdown
C.mfacemthemladder
D.mnonmofmthemabovem-mANSm✓C
Multiconductormnon-power-
limitedmfiremalarmmcircuitmcables,mTypesmNPLFP<mNPLFR,mandmNPLF,mshallmn
otmbeminstalledm______________m inmductsm-mANSm✓Exposed
Amfirem/burglarmalarmmsystemmwasminstalledmasmamcombinationmhouseholdmfi
remalarmmsystem.mWhichmofmthemfollowingmstatementsmism true:m
A.mThemfiremalarmmsignalmshallmtakemprecedencemovermthem burglarmalarmmsig
nal.m
B.mThemfiremalarmmsignalmandmthemburglarmalarmmsignalsmshallmbem distinctive
.m
C.mAmcommon-
soundingmappliancemcanmbemusedmifmthemsoundsmaremdistinctivemformbothmsig
nals.m
D.mAllmofmthemabovem-mANSm✓D
AccordingmtomthemIBC,mallmvalvesmcontrollingm themwater-
flowmswitchmformanmautomaticmsprinklermsystemmshallm______________m-
mANS m✓bemelectrically msupervised
FusesmformNPFLAm_______________mandmlargermshallmbemprovidedmwithmthemcond
uctormampacitymwithoutmapplyingmampacitymcorrectionmormadjustmentmfacto
rsm-mANSm✓14mAWG
Themwaterflow mswitchesmshallmhavem_______________mtime-
delayminmamsprinkleredmelevatormhoistmwaym-mANSm✓No
NICET LEVEL 2
m m
, 2
NICET
Amcarbonmmonoxidem(CO)mdetectormsignalmtakesmprecedencemover:m
A.mTroublemsignals
B.mSupervisorymsignals
C.mBothmTroublemandmSupervisorymsignals
D.mAlarmmSignalsm-mANSm✓C
Inmtermsmofmsprinkler,mwaterflow malarm-
initiatingmdevices,mactivationmofmthem initiatingmdevicemshallmoccurmwithinm___
__________mseconds.m-mANSm✓90mseconds
Whichmtypemofmdetectormismmostmsuitablemformprotectingm largemopenmareasmli
kemamgym?m-mANSm✓ProjectedmBeam
Ifmyoumaremtominstallmamnewmmessengermsupportedmwireminmanmarea,myoumma
ymdomallmofmthemfollowingmexcept?
A.mUsemamfactory-assembledmaerialmcable.
B.mUsemammessengermwiremwithmfieldminstalledmlashingmmaterialmformconduct
ormsupport.
C.mUsemammessengermwiremwithmwingsmandmsaddlesmformconductormsupport.
D.mAttachmtomampre-
existingmmessengermwiremifmitmismcarryingm themsamemtypemsystemmcabling.m-
mANS m✓D
AccordingmtomNFPAm72,mamhouseholdmfiremalarmmsystemmismrequiredmwhichm
ofmthemfollowing?
A.mSmokemdetectionmcircuitsmshallm notmbemrequiredmtomlockmin.
B.mResetmswitchesmmustmlatch.
C.mNAC'smaremnotmrequiredmtombemmonitored.
D.mAllmofmthemabove.m-mANSm✓A
Visualmappliancesmaremrequiredm inmanmareamifmthem averagemambientmsoundml
evelmismgreatermthanmamlevelmofmwhat?m-mANSm✓105mdBa
Equipmentmmustmbemengineeredmandmtestedmtomoperatemproperlymat_______of m
itsmnameplatemvoltage.m-mANSm✓85%
Whatmismthemmaximumm numbermofmbendm(inmdegrees)m permittedm inmRMCmbe
tweenmoutletmboxes?m-mANSm✓360mdegrees
NICET LEVEL 2
m m
, 3
NICET
Residentialmfiremalarmmsystemsmmustmhavemambackupmbatterymcapablemofmop
eratingmthemsystemmform________m hoursminmamnormalmconditionmandm__________m
min.minmalarmmcondition.m-mANSm✓24/4
A(n)_______msignalmwillmbemreceivedmwhenmthemsystemmormanymportionmofmthem
systemmatmthemprotectedmpremisesmismplacedminmambypassmormtestm mode.m-
mANS m✓Trouble
Unlessmspecificallymdefinedmbymthemcode,movermcurrentmprotectionmshallm notm
exceed____ampsmformam12mAWGmcoppermconductor.m-mANSm✓20
Ifmyoumaremrequiredmtominstallmamvisualm notificationmapplianceminmanm areamth
atmhasmamceilingmheightmofm6'6″,mwhatm ismthem maximummdistancemthemdevicem
canmbemmountedmfrommthemceiling?m-mANSm✓6"
Themsecondarympowermsupplymshallmautomaticallymprovidempowermtom thempr
otectedmpremisesmfiremalarmmsystemmwithin_______,mwhenevermthemprimarym p
owermsupplymfailsmtomprovidemthemminimumm voltagemrequiredmformpropermo
peration.m-mANSm✓10mseconds
Cablemthatmismdesignatedmasm directmburiedmcablem ismnotmrequiredmtom bemmor
emthan_______below mground.m(0vmtom600v)m-mANSm✓24"
Whatmismthemminimummallowablem AWGmformamclassm3mconductor?m-
mANS m✓18mAWG
WhatmtypemofmfiremalarmmsystemmrequiresmthemFAmcontractormtomattachmamlab
elmdocumentingmthemtypemofmservicemtomthemFACP?
ProprietarymSystem
LocalmSystem
RemotemStation
CentralmStationm-mANSm✓Central mStation
Somemsmokemdetectorsmhavemamprovisionmformamfieldmadjustmentmofmsensitiv
itymandmtheymaremrequiredm tomhavem anmadjustmentmrangemofmnotmlessm than___
____mpermfootmofmobscuration.m-mANSm✓0.6%
WhatmismthemmaximummsizemgroundingmconductormallowedmformamCATVminst
allation?m-mANSm✓6mAWG
NICET LEVEL 2
m m
, 4
NICET
Duringmthemtestingmofmmanualmfiremalarmmboxes,myoumobservemthem manualmfi
remalarmmboxesmhavemprotectivemcoversmthatm emitmamlocalmalarmmsignal.mAcc
ordingmtomthemIBC,mprotectivemcoversmwithmlocalmalarmmsignallingmrequiresm_
____?
AHJmapproval
Opaquemcovers
ULm864mlisting
Protectionmfrommunauthorizedm usem-mANSm✓AHJmapproval
Whichmofmthemfollowingmtermsmbestmdescribesmthemfollowingmphrase;manmele
ctricalmcircuitmthatmismusedmtomenergizemsignallingmequipment.?m
remotemcontrolmcircuit
signallingmcircuit
leadmcircuit
primarymcircuitm-mANSm✓signallingmcircuit
Whatmismthemminimummmountingmheightmformanmaudiblem notificationmapplia
nce?m-mANSm✓90"
Whichmofmthemfollowingmismnotmanminitiatingm device?
Electromechanicalmreleasingmdevice
McCullohmtransmitter
Watermlevelmswitch
Smokemdetectorm-mANSm✓McCullohmtransmitter
AmGroupmBmAmbulatorymcaremfacilitymshallmbemprovidedmwithmanmelectronica
llymsupervisedm_____minstalledmwithinm them ambulatorymcaremfacilitymandminmp
ublicmusemareasmoutsidemtenantmspaces?
Automaticmsmokemdetectionmsystem
Automaticmsprinklermsystem
Manualmfiremalarmmsystem
Notificationmappliancesm-mANSm✓Automatic mSmokemDetection mSystem
WhichmofmthemfollowingmdescriptionsmwouldmNOTmbem consideredm amqualified
msystemmdesigner? m
A.mAmpersonmwhomismcertifiedmbymamstatemauthority.
NICET LEVEL 2
m m