Where is the union A union fitting shall be provided for appliance
located for a gas connected by rigid metallic pipe. Such unions shall be
appliance? accessible and located within 6 feet of the appliance.
https://quizlet.com/1023158241/nyc-fuel-gas-code-final-exam-2025-newest-actual-exam-complete-questions-and-correct-detailed-answers-100-verifi… 1/11
, 3/26/25, 11:49 AM NYC FUEL GAS CODE FINAL EXAM 2025 NEWEST ACTUAL EXAM COMPLETE QUESTIONS AND CORRECT DETAILED AN…
Gas piping may be installed in public corridors in
residential buildings that do not have floors below
grade or in multi use buildings that have a residential
occupancy in accordance with the following, Gas
piping shall be permitted to be installed within a
public corridor at the lowest level of the building or
the lowest residential level of the building. All gas
Where is gas piping valves located within the public corridor shall be
permitted? accessible for maintenance and inspection. Gas
pressure within the public corridor piping shall not
exceed 1/2 psi. The completed piping within the
public corridor is to be tested and proven tight at 10
psig for a minimum of 30 minutes. The public corridor
shall be ventilated in accordance with the New York
City Mechanical Code. The pipe shall not be installed
in a return air plenum. Pipes must be welded.
How much must piping for Not less the 1/4 inch in 15 feet to prevent traps.
other than dry gas
conditions be sloped?
Hanger spacing for 3/4 8 feet
inch and 1 inch gas pipe
When is water permitted Fresh water may be used the test medium where the
for testing? required test pressure exceeds 100 p.s.i.g.
Expansion joints shall be provided with temporary
When do need temporary
restraints, if required, for the additional trust load
restraints when testing?
under test.
What must each digital The gauge shall have a minimum reading of 1/100 of a
gauge used to measure p.s.i.g.
pressure in the magnitude
of 3 and higher read?