\______________ can put out the flame - ANS-black smoke and soot
\____________requires that all fuel oil piping and storage tanks be hydrostatically tested at
150% of the maximum working pressure for tightness by the installing contractor before the
work is closed in and before the system is operated - ANS-the mechanical code
\________require that pipe shafts containing piping from transfer pumps to storage tanks
above the lowest floors not be penetrated by or contain other piping or ducts -
ANS-construction codes
\1000*F or greater under normal operating conditions - ANS-high temperature equipment is
rated at
\50% capacity is used for each pump when - ANS-three or more oil pumps are used
\600*F or under - ANS-equipment classification of low temperature equipment is rated at
\8k va - 200k va - ANS-large portable diesel generators that service office complexes,
factories and power stations range from
\a flame will have an orange colored flame body with small red tips - ANS-a correctly
adjusted burner
\a red Smokey flame is an indication of: - ANS-lack of air
\A stationary fuel oil storage tank, and related piping, that is installed on the lowest - ANS-
\a white almost dazxling flame is an indication of - ANS-excess air
\after any repair is made to the piping or oil burner equipment by a licensed or qualified
contractor(s), the system must be checked by: - ANS-the certificate of fitness holder
\all oil burning equipment and piping must be inspected at least: - ANS-weekly
\an insufficient air supply is one cause of: - ANS-dense black smoke and soot
\any potential or hazard where oil burning equipment systems are operated must be
corrected immediately by: - ANS-the representative of the manufacturer or authorized
professional in accordance with the manufacturer's instrucions
\at 150% of maximum working pressure - ANS-hydro static testing on piping shall be tested
\carbon dioxide and carbon monoxide - ANS-during the combustion process the carbon
content unites with oxygen in the air and forms
\Class A fires are caused by ordinary combustibles such as wood, paper, and cloths are
extinguished by - ANS-water
\class D fires are caused by ignitable metals such as calcium zinc and aluminum -
ANS-water should not be used to extinguish these fires
\clearances between oil fired equipment and oil supply tanks shall be in accordance with -
ANS-the construction codes, nyc building codes &
mechanical codes
\clearances between oil-fired equipment and oil supply tanks shall be in accordance with
_________ - ANS-The Construction codes
The NYC Building code and The Mechanical code
\During the combustion process, the carbon content unites with oxygen in the air and forms
what? - ANS-carbon dioxide and carbon monoxide
\excessive air - ANS-a white almost dazzling flame is an indication of what
- ANS-
\______________ can put out the flame - ANS-black smoke and soot
\____________requires that all fuel oil piping and storage tanks be hydrostatically tested at
150% of the maximum working pressure for tightness by the installing contractor before the
work is closed in and before the system is operated - ANS-the mechanical code
\________require that pipe shafts containing piping from transfer pumps to storage tanks
above the lowest floors not be penetrated by or contain other piping or ducts -
ANS-construction codes
\1000*F or greater under normal operating conditions - ANS-high temperature equipment is
rated at
\50% capacity is used for each pump when - ANS-three or more oil pumps are used
\600*F or under - ANS-equipment classification of low temperature equipment is rated at
\8k va - 200k va - ANS-large portable diesel generators that service office complexes,
factories and power stations range from
\a flame will have an orange colored flame body with small red tips - ANS-a correctly
adjusted burner
\a red Smokey flame is an indication of: - ANS-lack of air
\A stationary fuel oil storage tank, and related piping, that is installed on the lowest - ANS-
\a white almost dazxling flame is an indication of - ANS-excess air
\after any repair is made to the piping or oil burner equipment by a licensed or qualified
contractor(s), the system must be checked by: - ANS-the certificate of fitness holder
\all oil burning equipment and piping must be inspected at least: - ANS-weekly
\an insufficient air supply is one cause of: - ANS-dense black smoke and soot
\any potential or hazard where oil burning equipment systems are operated must be
corrected immediately by: - ANS-the representative of the manufacturer or authorized
professional in accordance with the manufacturer's instrucions
\at 150% of maximum working pressure - ANS-hydro static testing on piping shall be tested
\carbon dioxide and carbon monoxide - ANS-during the combustion process the carbon
content unites with oxygen in the air and forms
\Class A fires are caused by ordinary combustibles such as wood, paper, and cloths are
extinguished by - ANS-water
\class D fires are caused by ignitable metals such as calcium zinc and aluminum -
ANS-water should not be used to extinguish these fires
\clearances between oil fired equipment and oil supply tanks shall be in accordance with -
ANS-the construction codes, nyc building codes &
mechanical codes
\clearances between oil-fired equipment and oil supply tanks shall be in accordance with
_________ - ANS-The Construction codes
The NYC Building code and The Mechanical code
\During the combustion process, the carbon content unites with oxygen in the air and forms
what? - ANS-carbon dioxide and carbon monoxide
\excessive air - ANS-a white almost dazzling flame is an indication of what