WITH DETAILED VERIFIED ANSWERS
Terms in these 2 sets (86 and 200)
,what is the maximum 4 wires
number of 14 AWG RHH
conductors which can be
installed in 1/2 rigid metal
conduit?
Which of the following 3.5'-48" to the actuator
would be an appropriate
mounting height for a pull
station?
What is the minimum 1 flash per second
flash rate for a visible
notification device?
What is the 90" to the top of the device
minimum mounting
height for audible
notification devices?
What is the minimum mounting Such that the entire lens is not less then 80"
height for visible notification
devices?
What is the formula for Ohm's Voltage=Current X Resistence
Law
,When using your mult- Put your meter in series with the circuit
meter to measure, you must:
Waterflow devices shall be Semi-annually
tested with that frequency?
With what frequency shall Annually
ionization smoke detectors be
given a functional test?
What are the standby power 24 hours in normal operation, 5 minutes in alarm
requirements for a proprietary
signaling system?
Which of the following is a type Shunt type
of auxiliary protective signaling
system?
Remote station signaling A UL listed central station
systems are permitted to send A receiver located at an unlisted monitoring facility
signals to:
A fire department or communications center
Non-power limited fire alarm 600V
cable shall have an insulation
rating of:
Which of these HVAC systems 20,000 CFM HVAC system serving a single floor
would require duct detectors 15,000 CFM HVAC system serving 3 floors
on supply and return? 20,000 CFM HVAC system serving 2 floors
, According to the IBC, Group A, E, F
which of the following use
Groups require visual
notification?
Digital Alarm Every 4 hours
communicator
transmitters (DACT) which
use call forwarding to the
DACR shall be tested with
what frequency?
When connecting 4 wires True
smoke detectors to a fire
alarm system, the power
conductors shall be
monitored for integrity.
Which of the following is Smoke detectors shall be permitted to use 30 foot spacing as
true regarding smoke a guide
detector spacing?
A slope ceiling is defined A slope of greater than 1 in 8
as:
Fire alarm control equipment shall be protected with
an automatic detector when not in continuously
Which of the following is occupied areas
true? Positive alarm sequence requires the approval of the
AHJ
FPLP cable may be substituted with CMP cable