When charging a chiller, refrigerant vapor is introduced into the system before charging with liquid. This
is because: - Answers Liquid charged into a deep vacuum will cause the refrigerant to boil and may lower
temperature enough to freeze the water in the tubes.
A hydrostatic tube test kit is used to: - Answers Determine if a tube leaks.
A charged low pressure refrigeration system can be efficiently leak checked by: - Answers Raising system
pressure by heating with circulated hot water or heating blankets.
What is meant by the term "high efficiency purge unit"? - Answers Those purge units which discharge a
low percentage of refrigerant with the air which they remove.
On a low pressure chiller with an open type compressor, the _________________ is very susceptible to
leaks. - Answers Shaft seal.
The lowest access point on a low pressure centrifugal air conditioning unit is the: - Answers The
evaporator charging valve.
ASHRAE Standard 15-1994 requires that each machinery room must activate an alarm and mechanical
ventilation before refrigerant concentrations exceed: - Answers The TLV-TWA (Threshold Limit Value -
Time Weighted Average).
A typical setting for the high pressure cut out control on a recovery unit used for evacuating the
refrigerant from a low pressure chiller is: - Answers 10 psig.
On low pressure chillers, moisture typically enters the refrigerant system through: - Answers Air leaks
from the areas with gaskets or fittings.
Where does refrigerant go after it leaves the purge unit of a low pressure centrifugal system? - Answers
The evaporator.
Which repair WOULD NOT fall under the EPA definition for "MAJOR MAINTENANCE, SERVICE OR
REPAIR"? - Answers Replacing an oil filter.
The primary water source for a recovery unit condensing coil is _____________. - Answers Local
municipal water supply.
After recovering the liquid refrigerant you must: - Answers Recover the vapor refrigerant.
Refrigerant is added to a centrifugal machine through the: - Answers Evaporator charging valve.
The existence of air in a low pressure system, causes ______________. - Answers High head pressure.
The discharge from a rupture disc should be piped _________ for venting? - Answers Outdoors.
Refrigerant - 11 at a pressure of 17 inches Hg vacuum has a saturation temperature of: - Answers 35F.