Update 2025-2026 50 Questions and 100%
Verified Correct Answers Guaranteed A+
__________ CHECK VALVES ARE NORMALLY USED IN SYSTEMS USING A GATE
VALVE. - CORRECT ANSWER: SWING
__________ IS A DESIGNED SERIES OF BEAMS USED TO SUPPORT
MECHANICAL EQUIPMENT. - CORRECT ANSWER: DUNNAGE
__________ VALVES ARE USED TO SHUT DOWN PART OF THE SYSTEM WHEN
CONDUCTING REPAIRS OR MAINTENANCE. - CORRECT ANSWER: POST
INDICATOR
A ____________ TEST REQUIRES AT LEAST TWO INDIVIDUALS. - CORRECT
ANSWER: FULL FLOW TRIP
A FIRE DEPT. CONNECTION WAS FORMERLY KNOWN AS A ______________
CONNECTION. - CORRECT ANSWER: SIAMESE
A PRESSURE RESTRICTING DEVICE SHALL BE INSTALLED AT HOSE OUTLETS
WHERE STATIC PRESS. EXCEEDS ___________ PSI. - CORRECT ANSWER: 80
ACCEPTABLE AIR PRESSURE INSIDE AIR TANKS MAY VARY FROM ____________
PSI. - CORRECT ANSWER: 15-80
CHECK VALVES SHALL BE INSPECTED ___________ EVERY 5 YEARS. -
CORRECT ANSWER: INTERNALLY
, EXTERIOR SIGNAGE SHALL HAVE A __________ BACKGROUND WITH 1 INCH
HIGH ___________ LETTERS. - CORRECT ANSWER: WHITE, RED
FOR 1938-1968 HOSE OUTLET AND RELEASE RACKS, THE HOSE SHOULD BE
KEPT BETWEEN __________ FT AND ___________ FT ABOVE THE FLOOR OR
LANDING. - CORRECT ANSWER: 5, 6
HOSE MARKES "SUPPLY HOSE" SHALL NOT EXCEED __________ PSI. -
CORRECT ANSWER: 185
IF ENCLOSED IN A CABINET, THE HOSE RACK SHALL SWING OUT AT LEAST
____________. - CORRECT ANSWER: 90 DEGREES
IN ABSENCE OF A SPECIFIC DESIGNEE, THE BUILDING OWNER SHALL BE
CONSIDERED THE _____________. - CORRECT ANSWER: IMPAIRMNENT
COORDINATOR
IN AN OS&Y VALVE, IF THE STEM IS RAISED ABOVE THE CONTROL WHEEL THE
VALVE IS ___________. - CORRECT ANSWER: OPEN
INTERIOR SIGNAGE SHALL HAVE A ________ BACKGROUND WITH 1 INCH HIGH
__________ LETTERS. - CORRECT ANSWER: RED, WHITE
INTERIORS OF _________ TANKS SHALL BE INSPECTED EVERY 3 YEARS. -
CORRECT ANSWER: STEEL
IT IS __________ TO INSTALL OR MAINTAIN FIRE PROTECTION SYSTEMS THAT
HAVE THE PHYSICAL APPEARANCE OF FIRE EQUIPMENT BUT THAT DON'T
PERFORM A FUNCTION. - CORRECT ANSWER: UNLAWFUL