accurate.
A member of the LP Gas Board correct answers Other than a Deputy State Fire Marshal of the
Division of State Fire Marshal, who may be permitted to enter during reasonable business hours
to inspect your gas industry to assure the safety of the public?
An individual certified as competent by the Division of State Fire Marshal correct answers South
Carolina's laws regarding the retail sale of propane to the public require that the seller have a
license from the LP Gas Board and...?
Not to exceed 6 months from the date of installation correct answers According to the National
Fire Protection Association Pamphlet (NFPA) #58, what is the limit on a temporary installation?
1.0 lbs. per 10,000 gallons of LP-Gas correct answers The ratio of Ethyl Mercaptan per 10,000
gallons of LP Gas by test shall be how many lbs. per gallon?
U.S. Department of Transportation correct answers DOT containers shall be designed, fabricated,
tested, and marked (or stamped) in accordance with which organization?
120,000 water gallons correct answers Containers for general use shall not have individual water
capacities greater than how many gallons?
30,000 water gallons correct answers Service station containers shall not have individual
capacities greater than how many gallons?
Bathroom correct answers NFPA pamphlet #54 states that unvented space heaters are not to be
installed in which area?
, NFPA #58 as adopted by the LP Gas Board correct answers When LP-Gas and other compressed
gases are to be stored in the same area, the containers shall be marked according to which
regulatory agency?
Cast Iron correct answers What material may NOT be used under service conditions for
container appurtenances for LP Gas?
250 PSIG correct answers Container appurtenances shall have a rated working pressure of at
least what PSIG?
12 years from manufacture date and every 10 years thereafter correct answers All industrial
trucks, including fork lift containers in use shall have the pressure relief valve replaced at what
interval?
60 drill size opening correct answers Excess flow valves shall be designed to close automatically
at the rated flow of vapor or liquid specified by the manufacturer. Valves shall be designed with a
bypass, not to exceed what size drill opening?
To indicate the maximum filling level correct answers What is the purpose of a fixed liquid level
gauge on containers to be filled by volume?
Container opening or to a valve or fitting which is attached directly to container correct answers
Pressure gauges shall be installed in what part of a LP Gas System used in a bulk plant?
350 PSIG correct answers Fittings used at pressures higher than container pressure on the
discharge of the liquid transfer pump shall be suitable for a working pressure of at least how
much PSIG?
250 PSIG correct answers Fittings used with liquid LP Gas or with vapor LP Gas at operating
pressures over 125 PSIG shall have a working pressures of what PSIG?