Geschreven door studenten die geslaagd zijn Direct beschikbaar na je betaling Online lezen of als PDF Verkeerd document? Gratis ruilen 4,6 TrustPilot
logo-home
Tentamen (uitwerkingen)

ABYC Marine Electrical Certification Exam Questions with Correct Verified Answers, Already Passed! (Complete & Accurate)

Beoordeling
-
Verkocht
-
Pagina's
63
Cijfer
A+
Geüpload op
07-06-2025
Geschreven in
2024/2025

ABYC Marine Electrical Certification Exam Questions with Correct Verified Answers, Already Passed! (Complete & Accurate) T or F: A battery charger case shall be tied to the DC negative output terminal at the battery charger. - ANS False. the battery charger case shall be tied to the engine negative terminal/bus, along with the negative output terminal of the battery charger, not at the battery charger case itself., Why do battery chargers require a separate case connection to main AC grounding bus and Engine negative / DC grounding bus? - ANS In case of an internal short to the case, the AC grounding wire would not carry enough current. What is the minimal wire size required for a battery charger case connection to DC ground/engine negative? - ANS No smaller than 1 size below the DC current carrying conductors between the charger and batteries - provided OC protection on positive DC output is no greater than 135% of DC grounding cable ampacity and conductor is no smaller than 16 AWG. What device is typically found to satisfy the required OC protection between a battery charger and the batteries? - ANS Class T fuse rated for appropriate AIC What may happen to a solar array or wind generator used to charge batteries without a blocking diode? - ANS Batteries will feed back into solar array or wind generator coil and discharge (possibly damage). Note: many voltage regulators have integral blocking diodes. How far above bilge water level must a battery charger be mounted? - ANS 24 inches or more (unless waterproof!) How far away from a gasoline tank must a pre-wired battery charger's AC connection plug be located? - ANS At least 24 inches T or F: All marine inverters shall utilize an internal or external GFCI on their AC outlets. - ANS False. (only when installed in location that required GFCI per ABYC E-11) T or F: most GFCI outlets can be used in a gasoline engine room - ANS False. Most are not ignition protected. T or F: Because the shore power connection is a power source, the neutral conductor should be tied to ground at the point where it comes in to the boat (shore power cable connection) - ANS False. Shore power neutral is tied to ground on the shore side. Tech A says that voltage supplied to the rotor controls the alternator output voltage. Tech B says that the alternator output is proportional to the rotor voltage. Which is correct, A, B, Both or Neither? - ANS Both. Tech A says that AC and DC are able to run together down the same conductor. Tech B says this is technically impossible. Which is correct, A, B, neither or both? - ANS Tech A According to ABYC, what is the maximum distance allowed between a boat's shore power connection and the main overcurrent protection device? - ANS 10' What is an ELCI and where is it required to be installed? - ANS Equipment Leakage Current Interrupter - within 10 feet of shore power connection unless an isolation transformer is located within 10' of shore power connection. T or F: When more than one option for shore power inlet is installed on a boat, the shore power neutrals shall be tied together on the boat. - ANS False, they must be isolated to prevent shock hazard at the unutilized shore power connector pins. What ampacity is required for wire and terminals connecting a galvanic isolator? - ANS At least 135% of isolator’s nominal rating. (A-28.11.1)

Meer zien Lees minder
Instelling
Vak

Voorbeeld van de inhoud

1
ABYC




ABYC Marine Electrical Certification Exam
Questions with Correct Verified Answers,
Already Passed! (Complete & Accurate)
T or F: A battery charger case shall be tied to the DC negative output
terminal at the battery charger. - ANS ✓False. the battery charger case
shall be tied to the engine negative terminal/bus, along with the negative
output terminal of the battery charger, not at the battery charger case
itself.,


Why do battery chargers require a separate case connection to main
AC grounding bus and Engine negative / DC grounding bus? - ANS ✓In
case of an internal short to the case, the AC grounding wire would not carry
enough current.


What is the minimal wire size required for a battery charger case
connection to DC ground/engine negative? - ANS ✓No smaller than 1
size below the DC current carrying conductors between the charger and
batteries - provided OC protection on positive DC output is no greater than
135% of DC grounding cable ampacity and conductor is no smaller than 16
AWG.


What device is typically found to satisfy the required OC protection
between a battery charger and the batteries? - ANS ✓Class T fuse rated
for appropriate AIC




ABYC Marine Electrical Certification

, 2
ABYC

What may happen to a solar array or wind generator used to charge
batteries without a blocking diode? - ANS ✓Batteries will feed back into
solar array or wind generator coil and discharge (possibly damage). Note:
many voltage regulators have integral blocking diodes.


How far above bilge water level must a battery charger be mounted? -
ANS ✓24 inches or more (unless waterproof!)


How far away from a gasoline tank must a pre-wired battery charger's
AC connection plug be located? - ANS ✓At least 24 inches


T or F: All marine inverters shall utilize an internal or external GFCI
on their AC outlets. - ANS ✓False. (only when installed in location that
required GFCI per ABYC E-11)


T or F: most GFCI outlets can be used in a gasoline engine room - ANS
✓False. Most are not ignition protected.


T or F: Because the shore power connection is a power source, the
neutral conductor should be tied to ground at the point where it
comes in to the boat (shore power cable connection) - ANS ✓False.
Shore power neutral is tied to ground on the shore side.


Tech A says that voltage supplied to the rotor controls the alternator
output voltage. Tech B says that the alternator output is proportional
to the rotor voltage. Which is correct, A, B, Both or Neither? - ANS
✓Both.


Tech A says that AC and DC are able to run together down the same
conductor. Tech B says this is technically impossible. Which is correct,
A, B, neither or both? - ANS ✓Tech A

ABYC Marine Electrical Certification

, 3
ABYC



According to ABYC, what is the maximum distance allowed between a
boat's shore power connection and the main overcurrent protection
device? - ANS ✓10'


What is an ELCI and where is it required to be installed? - ANS
✓Equipment Leakage Current Interrupter - within 10 feet of shore power
connection unless an isolation transformer is located within 10' of shore
power connection.


T or F: When more than one option for shore power inlet is installed
on a boat, the shore power neutrals shall be tied together on the boat.
- ANS ✓False, they must be isolated to prevent shock hazard at the
unutilized shore power connector pins.


What ampacity is required for wire and terminals connecting a
galvanic isolator? - ANS ✓At least 135% of isolator’s nominal rating. (A-
28.11.1)


What is the general rule for use of friction connectors? - ANS
✓Ampacity < 20 Amps, voltage drop across terminals < 50 mV @ 20 A flow,
no separation with a one-minute pull of 6 lb force.


When measuring temperature to determine potential electrical issues
involving excessive connector resistance, what is the threshold for
concern? - ANS ✓> 25 degrees above ambient


According to the ABYC, the shore-power grounded conductor should:
A. Be connected to the AC neutral
B. Not be grounded on the boat


ABYC Marine Electrical Certification

, 4
ABYC

C. Be connected to the engine common positive terminal or its bus
D. Be tied to the battery isolator - ANS ✓B. Not be grounded on the boat


If a customer complains about receiving shocks from her boat when
shore power is active, the technician should first test:
A. Polarity check of shore cord
B. Polarity check of the battery system
C. Current Leakage Test
D. Converter voltage check - ANS ✓A. Polarity check of shore cord


A customer is complaining about low-voltage at the AC panel. What
should you do first?
A. Re-calibrate the panel meter
B. Check the voltage at the dock pedestal
C. Check the polarity indicator
D. Replace the overcurrent device - ANS ✓B. Check the voltage at the
dock pedestal


A customer notes a reverse-polarity problem. All of the following are
likely causes, except:
A. Improperly wired shore power cord
B. Improperly wired shore power inlet receptacle
C. An open neutral
D. Reversal of the hot and neutral conductors in the AC panel feeder
cable - ANS ✓C. An open neutral


What is a likely cause of non-functioning galvanic isolator?



ABYC Marine Electrical Certification

Geschreven voor

Vak

Documentinformatie

Geüpload op
7 juni 2025
Aantal pagina's
63
Geschreven in
2024/2025
Type
Tentamen (uitwerkingen)
Bevat
Vragen en antwoorden

Onderwerpen

$13.99
Krijg toegang tot het volledige document:

Verkeerd document? Gratis ruilen Binnen 14 dagen na aankoop en voor het downloaden kun je een ander document kiezen. Je kunt het bedrag gewoon opnieuw besteden.
Geschreven door studenten die geslaagd zijn
Direct beschikbaar na je betaling
Online lezen of als PDF


Ook beschikbaar in voordeelbundel

Maak kennis met de verkoper

Seller avatar
De reputatie van een verkoper is gebaseerd op het aantal documenten dat iemand tegen betaling verkocht heeft en de beoordelingen die voor die items ontvangen zijn. Er zijn drie niveau’s te onderscheiden: brons, zilver en goud. Hoe beter de reputatie, hoe meer de kwaliteit van zijn of haar werk te vertrouwen is.
NurseAdvocate chamberlain College of Nursing
Volgen Je moet ingelogd zijn om studenten of vakken te kunnen volgen
Verkocht
497
Lid sinds
2 jaar
Aantal volgers
77
Documenten
12046
Laatst verkocht
3 dagen geleden
NURSE ADVOCATE

I have solutions for following subjects: Nursing, Business, Accounting, statistics, chemistry, Biology and all other subjects. Nursing Being my main profession line, I have essential guides that are Almost A+ graded, I am a very friendly person: If you would not agreed with my solutions I am ready for refund

4.6

239 beoordelingen

5
193
4
14
3
15
2
6
1
11

Recent door jou bekeken

Waarom studenten kiezen voor Stuvia

Gemaakt door medestudenten, geverifieerd door reviews

Kwaliteit die je kunt vertrouwen: geschreven door studenten die slaagden en beoordeeld door anderen die dit document gebruikten.

Niet tevreden? Kies een ander document

Geen zorgen! Je kunt voor hetzelfde geld direct een ander document kiezen dat beter past bij wat je zoekt.

Betaal zoals je wilt, start meteen met leren

Geen abonnement, geen verplichtingen. Betaal zoals je gewend bent via iDeal of creditcard en download je PDF-document meteen.

Student with book image

“Gekocht, gedownload en geslaagd. Zo makkelijk kan het dus zijn.”

Alisha Student

Bezig met je bronvermelding?

Maak nauwkeurige citaten in APA, MLA en Harvard met onze gratis bronnengenerator.

Bezig met je bronvermelding?

Veelgestelde vragen