Question #: 1: When troubleshooting a motor capacitor, the
|\ |\ |\ |\ |\ |\ |\ |\ |\
meter pegs to the right and stays there. What does this indicate?
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
- CORRECT ANSWERS ✔✔Correct answer: bad capacitor
|\ |\ |\ |\ |\ |\ |\
Additional Notes: If the capacitor were good, the needle would
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
peg to the right, then slowly drop back down.
|\ |\ |\ |\ |\ |\ |\ |\
Question #: 2: On a 480 V, three-phase blower motor with
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
auxiliary contacts and indicators, the push button start is off due
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
to a thermal overload. What is the most likely cause? - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔Correct answer: overloaded motor |\ |\ |\ |\
When installing a fire alarm system bell or horn, how far above
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
grade should it be mounted? - CORRECT ANSWERS ✔✔7'-6"
|\ |\ |\ |\ |\ |\ |\ |\
Additional Notes: The top of the device should be at least 7'-6"
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
above the finished floor and at least 6" below the finished ceiling.
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
If the ceiling height is too low to allow the recommended
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
mounting heights, the device can be mounted at a lower height,
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
or on the ceiling.
|\ |\ |\
What is the minimum length of a grounding rod? - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔8' |\
When testing a GFCI trip, probe conductor and fixture ground,
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
use: - CORRECT ANSWERS ✔✔inductive voltage tester
|\ |\ |\ |\ |\ |\
,On a walk-through of a new home, the owner wants you to install
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
an outlet beside the stove. The counter top is 48" long and the
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
wall is 6' away. The contractor - CORRECT ANSWERS ✔✔would
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
need to install 2 outlets
|\ |\ |\ |\
What is the maximum allowed gap allowed around a box in a wall
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
finished with drywall? - CORRECT ANSWERS ✔✔Correct answer:
|\ |\ |\ |\ |\ |\ |\ |\ |\
1/8" |\
Additional Notes: Plaster, drywall, or plasterboard surfaces must |\ |\ |\ |\ |\ |\ |\ |\
not have gaps or open spaces greater than 1/8" at the edge of a
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
box or fitting.
|\ |\
What is the minimum number of branch circuits required at each
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
patient bed location? - CORRECT ANSWERS ✔✔Correct answer:
|\ |\ |\ |\ |\ |\ |\ |\
two; one from the emergency electrical system and the other
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
from the normal system
|\ |\ |\
When can you have an isolated ground passing through a panel
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
without connecting it to that panel's equipment grounding
|\ |\ |\ |\ |\ |\ |\ |\
terminal bar? - CORRECT ANSWERS ✔✔Correct answer: when you
|\ |\ |\ |\ |\ |\ |\ |\
are reducing vibration and noise on the ground
|\ |\ |\ |\ |\ |\ |\ |\
Additional Notes: When installing an isolated ground receptacle |\ |\ |\ |\ |\ |\ |\ |\
the insulated equipment grounding conductor is run with the
|\ |\ |\ |\ |\ |\ |\ |\ |\
circuit conductors directly back to the main service disconnect.
|\ |\ |\ |\ |\ |\ |\ |\ |\
Metal boxes and raceways must still be grounded.
|\ |\ |\ |\ |\ |\ |\
Which of the following could cause a significant increase to the
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
bid amount on a job at an automotive repair shop? - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔Correct answer: the service pit is inadequately |\ |\ |\ |\ |\ |\ |\ |\
ventilated
, Additional Notes: The entire area of repair garages, up to a level |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
of 18" above the floor, are Class I, Division 2, locations. Any
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
depression below floor level (such as a service pit) is also a Class |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
I, Division 2, location unless it is unvented in which case it may
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
be considered a Class I, Division 1, location and require special
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
fittings.
What would you use in a capacitive reactance circuit to balance
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
the circuit? - CORRECT ANSWERS ✔✔inductor
|\ |\ |\ |\ |\
Which of the following NEMA rating should be used for temporary
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
construction power enclosures outside? - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\ |\
✔✔Correct answer: NEMA 3R |\ |\ |\ |\
Additional Notes: Enclosures with a NEMA rating of 3R is |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
designed for indoor or outdoor use. Enclosures with ratings of 1,
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
2, or 12 are designed for indoor use only.
|\ |\ |\ |\ |\ |\ |\ |\
What is the full-load current rating of a 208-volt, 50-horsepower,
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
three-phase squirrel-cage motor? - CORRECT ANSWERS |\ |\ |\ |\ |\ |\
✔✔Correct answer: 103 amps |\ |\ |\ |\
Additional Notes: To find the amperage of a three-phase motor |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
when you know the horsepower you use a variation of Watt's
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
Law: |\
I = (horsepower x 746 watts/horsepower) / (E x 1.73)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
I = (50 hp x 746 watts/hp) / (208 volts x 1.73) = 37,300 watts /
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
360 volts = 103 amps |\ |\ |\ |\