Dead-end corridors are limited to ___ feet in new and existing health
care occupancies. --- correct answer ---30 feet
For new health care occupancies, the travel distance between any
point in a room and an exit may not exceed _____. --- correct answer -
--200 ft
The travel distance between any point in a health care sleeping room
and an exit access door in that room may not exceed ____. --- correct
answer ---50 feet
A common path of travel in a new health care occupancy may not
exceed ___. --- correct answer ---100 feet
In a new health care occupancy what distance must separate the two
exit access doors?
A. One-third of the building or area's longest wall
, B. One-third of the building or area diagonal measurement
C. One-fourth of the building or area's longest wall
D. One-fourth of the building or area diagonal measurement ---
correct answer ---B. one-third of the building or area diagonal
measurement
Which of the following statements about areas of refuge is true?
A. An area of refuge must have smoke-resisting partitions.
B. An area of refuge must have sprinkler protection.
C. The Code requires areas of refuge in all buildings.
D. Supplemental requirements, such as a two-way communication
system apply to areas of refuge. --- correct answer ---D. Supplemental
requirements, such as a two-way communication system apply to
areas of refuge.
Intervening rooms in a patient sleeping room with not more than
eight beds:
A. Are limited to one per room
B. Are limited to two per room
C. Are limited to three per room
D. Are not limited in number --- correct answer ---D. Are not limited
in number