Verified 100% Correct
more than 36 inches - ANSWER The center of a hose outlet shall not be _______
above final grade
less than 150 psi - ANSWER All piping used in private fire service mains shall be rated
for the maximum system working pressure to which the piping is exposed to but shall
not be rated at _______________
asphalt or other corrosion-retarding material - ANSWER All bolted joint accessories
shall be cleaned and thoroughly coated with _______________ after installation
not be less than 30 inches - ANSWER In locations where freezing is not a factor, the
depth of cover shall __________________ below grade to prevent mechanical damage.
minimum depth of 36 inches - ANSWER Private fire service mains installed under
driveways or roadways shall be buried at a ______________
run in a covered trench - ANSWER Where private fire mains extend more than 10 ft
into the building, they shall be ___________
1 part cement, 2 1/2 parts sand, and 5 parts stone - ANSWER Thrust blocks shall be
concrete of a mix not leaner than ______________
not less than 5/8 in diameter - ANSWER Rods shall be _____________
shall be cleaned and thoroughly coated with a bituminous or other acceptable
corrosionretarding material - ANSWER After installation, rods, nuts, bolts, washers,
clamps, and other restraining devices _____________________
restrained at the bottom of a hill and at any lateral or vertical turns - ANSWER Pipe
shall be _____________________
facing uphill - ANSWER Bell ends shall be __________
clear of debris - ANSWER The flushing operation shall continue until water flow is
verified to be ___________
completing and signing the contractors material and test certificates - ANSWER The
installing contractor shall be responsible for _______________________