S-12 CITYWIDE SPRINKLER
SYSTEMS, S12 sprinkler test
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - answer OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES
FOR A MIN. OF __________ YEARS. - answer3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - answer IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - answer1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - answer1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED
TO SERVICE WITHIN ______ HOURS. - answer8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. -
answerOWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - answer30
WHAT DOES "OOS" STAND FOR? - answerOUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER -
answerTAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND
ANY SECTIONAL VALVES. - answerMASTER FIRE SUPPRESSION PIPING
CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER. - answerDRAIN TEST RESULTS
,GREEN TAGS INDICATE THAT __________. - answerNO IMPAIRMENT WAS
FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - answerMAIN CONTROL
VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________
TAG PLACED ON THE MAIN CONTROL VALVE. - answerRED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - answerWHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - answerBLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS. - answerINSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE
THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. -
answerIMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING. - answer50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR
THE ____________. - answerMAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE
FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. -
answerRECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS. - answerREVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS: - answerREFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH
PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS. - answerMASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)
, A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS. - answer30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED
WHEN SPRINKLERS ARE INSTALLED. - answer96
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING. - answer40 FAHRENHEIT
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. -
answerCOLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING. - answerDRY PIPE
THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. -
answerAIR PRESSURE
IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE
ALARM IS TRANSMITTED DIRECTLY TO THE _________. - answerFIRE
DEPARTMENT
DRY PIPE VALVES ARE OF A ______ DESIGN. - answerCLAPPER
DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE NORMAL
TRIP LEVEL. - answer15-20
AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME TO
ALLOW WATER INTO THE SYSTEM. - answerREDUCE
BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP OF
_______ PSI IS DETECTED IN THE SYSTEM. - answer2
IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE
SPRINKLER HEADS. - answerPREACTION VALVE
PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE _________ IS
OPENED. - answerVALVE
THREE DEVICES USED TO TRIP PREACTION VALVES ARE FIXED TEMP
DEVICES, RATE DEVICES, AND ___________ DEVICES. - answerCOMBINATION
THE _________ FEATURE SHUTS OFF WATER WHEN THE FIRE IS
EXTINGUISHED AND TURNS ON AGAIN IF THE FIRE REKINDLES. -
answerRECYCLING
SYSTEMS, S12 sprinkler test
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - answer OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES
FOR A MIN. OF __________ YEARS. - answer3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - answer IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - answer1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - answer1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED
TO SERVICE WITHIN ______ HOURS. - answer8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. -
answerOWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - answer30
WHAT DOES "OOS" STAND FOR? - answerOUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER -
answerTAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND
ANY SECTIONAL VALVES. - answerMASTER FIRE SUPPRESSION PIPING
CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER. - answerDRAIN TEST RESULTS
,GREEN TAGS INDICATE THAT __________. - answerNO IMPAIRMENT WAS
FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - answerMAIN CONTROL
VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________
TAG PLACED ON THE MAIN CONTROL VALVE. - answerRED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - answerWHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - answerBLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS. - answerINSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE
THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. -
answerIMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING. - answer50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR
THE ____________. - answerMAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE
FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. -
answerRECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS. - answerREVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS: - answerREFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH
PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS. - answerMASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)
, A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS. - answer30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED
WHEN SPRINKLERS ARE INSTALLED. - answer96
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING. - answer40 FAHRENHEIT
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. -
answerCOLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING. - answerDRY PIPE
THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. -
answerAIR PRESSURE
IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE
ALARM IS TRANSMITTED DIRECTLY TO THE _________. - answerFIRE
DEPARTMENT
DRY PIPE VALVES ARE OF A ______ DESIGN. - answerCLAPPER
DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE NORMAL
TRIP LEVEL. - answer15-20
AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME TO
ALLOW WATER INTO THE SYSTEM. - answerREDUCE
BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP OF
_______ PSI IS DETECTED IN THE SYSTEM. - answer2
IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE
SPRINKLER HEADS. - answerPREACTION VALVE
PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE _________ IS
OPENED. - answerVALVE
THREE DEVICES USED TO TRIP PREACTION VALVES ARE FIXED TEMP
DEVICES, RATE DEVICES, AND ___________ DEVICES. - answerCOMBINATION
THE _________ FEATURE SHUTS OFF WATER WHEN THE FIRE IS
EXTINGUISHED AND TURNS ON AGAIN IF THE FIRE REKINDLES. -
answerRECYCLING