Ampacity of branch circuit conductors must be derated when - ANS - There are more
than 3 conductors, temperature exceeds the temperature rating
Branch circuit conductors must have an ampacity rating equal to or greater than the non
continuous load plus - ANS - 125% of the continuous load
Continuous loads are calculated at - ANS - 125% of the maximum current rating
If the number of current carrying conductors in the conduit or cable exceeds three it
must be - ANS - derated
NEC Article 100 - ANS - A multi outlet assembly is defined as a type of surface flash
or freestanding raceway design to hold conductors and receptacles
NEC article 210 - ANS - Covers branch circuits ( except for branch circuits that
supplies only motor loads).
NEC Article 220 - ANS - Includes the requirements used to determinable the number
of branch circuits required and the requirements used to compute branch circuit feeder
and service loads
NEC article 424 - ANS - Covers fixed electric space heating equipment including
heating to cable unit heaters boiler central systems and other approved heating
equipment
NEC section 210.11 210.52 - ANS - Require at least 2 20A small appliance branch
circuits to be installed to supply receptacles in kitchen pantry breakfast room dining
room
NEC section 210.18 - ANS - Branch circuits are rated by the maximum rating or
setting of the over current device
NEC section 210.19 - ANS - Branch circuit conductors are required to be sized with
an ampacity rating that is no less than the maximum load to be served