NICET FIRE ALARM LEVEL I ACTUAL EXAM PREPARATION
NEWEST 2025/2026 NEWEST ACTUAL EXAM WITH
COMPLETE QUESTIONS AND VERIFIED ANSWERS
|ALREADY GRADED A+|
Which type of fire alarm key blank must be used for a run that will
be installed in a Plenum space? - ANSWER-FPLP
It technician notices that a step is missing from the letter which
two are the current courses of action? - ANSWER-Notify a
supervisor; Tag the ladder to prevent others from using it.
The minimum size for EMT is - ANSWER-1/2 inch
The maximum size fro EMT is - ANSWER-4 inches
EMT shall be securely fastened in place at least every -
ANSWER-10 feet
A load where the maximum current is expected to continue for 3
hours or more. - ANSWER-Continuous Load
, Page |2
The maximum current, in amperes, that a conductor can carry
continuously under the conditions of use without exceeding its
temperature rating. - ANSWER-Ampacity
A device intended to provide protection from the effects of arc
faults by the recognizing characteristics unique to arcing and by
functioning to de-energize the circuit what an arc fault is detected
- ANSWER-Arc-Fault Circuit Interrupter (AFCI)
The circuit conductors between the final overcurrent device
protecting the circuit and the outlet(s), - ANSWER-Branch Circuit
Any current in excess of the rated current of equipment of the
ampacity of a conductor. It may result from overload, short circuit,
or ground fault. - ANSWER-Overcurrent
The maximum height for initiating pull box - ANSWER-48 inches
, Page |3
How long shall a secondary power supply's capacitance last when
primary power is off? - ANSWER-24 hours non-alarm and 5
minutes of evacuation at the end.
The secondary power supply for in-building mass notification
system (MNS) shall last how long? - ANSWER-24 hours non-
alarm and 15 minutes during emergency.
The secondary power supply for in-building Fire emergency
voice/alarm communications shall last how long? - ANSWER-24
hours non-alarm and 15 minutes alarm
Trouble signals and their restoration to normal shall be indicated
within - ANSWER-200 seconds
Which circuit class is a fail-safe circuit? - ANSWER-Class D
A circuit class is not monitored for integrity? - ANSWER-Class E