All devices shall be located and mounted so that jarring or
vibration will not cause accidental operation.
A. True
B. False - Answer-A. True
The number of supervisory devices permitted to be
connected to a single initiating device circuit shall not
exceed 24.
A. True
B. False - Answer-B. False
All extinguishment systems having automated detection
equipment for activation shall also have means for manual
activation.
A. True
B. False - Answer-A. True
,2|Page
IN building protected throughout by an approved
supervised automatic fire detection system or approved
supervised automatic sprinkler system, doors in low and
ordinary hazard areas may be equipped with approved
listed locking devices that shall...
A. unlock upon actuation of the sprinkler system
B. unlock upon activation of the detection system
C. unlock upon loss of power controlling lock
D. release within 15 seconds whenever a force of 15 lbs.
is continually applied for not more than 3 seconds
E. all of the above
F.A,B and C - Answer-E. all of the above
A manual fire alarm station shall be provided in the natural
path of escape near each required exit. Additional manual
fire alarm stations shall be so located that the horizontal
distance to reach a station shall not exceed:
A. 100 feet
B. 200 feet
C. 50 feet
D. 250 feet - Answer-B. 200 feet
, 3|Page
Fire alarm system installation, wiring, or other
transmission path shall be monitored for integrity:
A. True
B. False - Answer-A. True
The failure of the DACT transmission channel requires that
a trouble be sent over the other channel within:
A. 10 minutes
B: 90 seconds
C. 4 minutes
D. 30 minutes - Answer-C. 4 minutes
Spare DACR's shall be provided in the supervising station
and shall be able to be switched into place of a failed unit
within:
A .90 seconds
B. 4 minutes
C. 30 seconds
D. 30 minutes - Answer-C. 30 seconds