2025-2026 Complete 300 Questions And Correct
Answers (Verified Answers)|Already Graded A
The operable part of a manually actuated alarm initiating device shall
be not less than ____ inches AFF...ANSWER..42 inches
Consider the use of grounding electrodes. Rod and pipe electrodes shall
not be less than____ feet in length?..ANSWER..8 feet
Smoke detectors should not be located in a direct airflow or closer than
____ inches from an air supply diffuser or return air
opening?..ANSWER..36 inches
Consider the use of visible notification appliances. Wall mounted
appliances shall be mounted such that the entire lens is not less than
____ inches above the finished floor?..ANSWER..80 inches
How many 16 gauge conductors are permitted in a 4 x 1 1/2 inches
square box?..ANSWER..12
Wall mounted audible appliances shall have their tops above the
finished floors at heights of not less than ____ inches and below the
finished ceilings at distances of not less than 6 inches?..ANSWER..90
inches
A minimum ____ db ambient sound level with a 6 hour exposure time
requires hearing protection?..ANSWER..92 db
,Spot type heat sensing fire detectors shall be located on the ceiling not
less than ____ inches from the sidewall...ANSWER..4 inches
While operating an aerial lift, the use of a body harnes and ____ is not
required?..ANSWER..Stabilizer Hook, Grounding Pole, Insulation Mat
Spot type smoke detectors shall be located on the ceiling or, if on a
sidewall, between the ceiling and ____ inches down from the ceiling to
the top of the detector...ANSWER..12 inches
The distance between spot type heat detectors shall not exceed their
listed spacing, and there shall be detectors within a distance of ____
the listed spacing, measured at right angles from the
walls?..ANSWER..One Half
Where partitions extend to within ____ percent of the ceiling height,
the spaces separated by the partitions shall be considered as separate
rooms?..ANSWER..15 percent
Consider 1,000 feet total of 18 gauge soild coated copper at 167o
Fahrenheit. The resistance of this conductor is ____
ohm?..ANSWER..8.08 ohm
2|Page
, Consider the installation of heat detectors on a ceiling with beams. A
ceiling shall be treated as a smooth ceiling if the beams project no more
than____ inches below the ceiling?..ANSWER..4 inches
Which of the following conductor types is an acceptable substitute for
FPLR?..ANSWER..FPLP, CMP
Consider the use of PLFA fire alarm cable. The size of conductors in
multiconductor cable shall not be smaller than____
AWG?..ANSWER..26 AWG
You are using a power tool that has a 3 prong (grounded) plug. The only
outlets available are 2 prong (non grounded). What can be
done?..ANSWER..Locate a 3 prong plug or used a tool with a 2 prong
plug.
The power source for a power limited fire alarm circuit shall be a listed
PLFA or Class ____ transformer?..ANSWER..Class 3 transformer
Which of the following is a symptom of heat stroke?..ANSWER..Red
skin, Elevated Body Temperature, Rapid, Weak pulse
The maximum number of 14 AWG, RHH conductors permitted in 1/2
inch EMT is ____?..ANSWER..4
3|Page