the following is required to be printed on the label of a gas
appliances - Answer-model number. serial number. btu
rating.
Gas appliances shall not be permitted to be installed
in___. - Answer-bathrooms
Appliances installed in a pit shall have a clearance from
the sides and bottoms of the pit of how many inches? -
Answer-12"
When calculating the opening for indoor combustion air for
combining spaces on the same story, the minimum free
area shall be _____ square inches for every 1000 Btu/h of
the total input rating of all appliances in the space. -
Answer-1
, 2|Page
Combustion air communicating directly with the outdoors
with two permanent openings shall have an opening of 1
square inches for every _____ Btu/h rating of the total of
all appliances served. - Answer-4,000
What is the assumed opening percentage for a wood
louver? - Answer-25%
Appliances installed in public garages shall be not less
than _____ feet above the floor. - Answer-8'
A level working space of not less than ____ inches wide
shall be provided on the control side of appliances. -
Answer-30"
What is the minimum height for a passageway into an
attic? - Answer-30"
What is the minimum width for the solid continuous
flooring for a passageway in an attic? - Answer-24"