Ceilings that have solid structural or solid nonstructural members
projecting down from the ceiling surface more than 4 in. and
spaced more than 36 in apart, center to center. - ANSWER-Beam
Construction
Actuation of alarm notification appliances or EVC's, emergency
control function interface devices, and annunciation at the
protected premises shall occur within - ANSWER-10 seconds
indication and restoring of self-restoring supervisory device shall
be automatically indicated within - ANSWER-90 seconds
Maximum air sample transport time from the farthest sampling
port to the detector shall not exceed - ANSWER-120 seconds
Wire splices angle or are you polls are made, the distance
between each raceway entry inside the box or condo and body
,2|Page
and the opposite wall of the box or kind a wood-burning or not be
less than - ANSWER-6 times the trade size of the largest raceway
in a row.
Vertical runs of a metal wireway shall be securely supported at
intervals not exceeding - ANSWER-15 feet
When a device is inaccessible due to excessive height, such as
an atrium, what it the maximum interval for testing? - ANSWER-
18 months
When installing a wall-mounted fire telephone appliance to the
public, what is the acceptable maximum mounting height from the
floor? - ANSWER-66 inches
Elevator lobby smoke detectors shall be mounted within a
maximum of which distance from the center-line of the door? -
ANSWER-21 feet
At minimum, when working near power lines with voltage of 600
volts and lower, an aerial lift operator shall maintain which
distance from the lines? - ANSWER-10 feet
, 3|Page
The use of unprotected EMT shall be permitted under which
conditions? - ANSWER-when in direct contact with the earth
According to NFPA 70, what is the maximum unsupported length
of 1/2-inch flexible metallic conduit where flexibility is required
after installation? - ANSWER-4 1/2 feet
What is the maximum bend (in degrees) permitted in a conduit
run between outlet boxes? - ANSWER-360 Degrees
If the primary power is disconnected and the fire alarm system
goes into an alarm condition, what is the minimum acceptable
time for secondary power to operate the voice evacuation
systems? - ANSWER-15 minutes
A riser room temperature switch should activate when the
temperature falls below which level? - ANSWER-40 degrees F