article 210.52 (B) (2) exceptions
In a single - family DWELLING BASEMENT which has two
entrances, how many LIGHTING OUTLETS are required where
the basement is used for STORAGE only?
A) 0
B) 1
C) 2
D) 3 - ANSWER-1
article 210.70 (A) (3)
What is the minimum wiring space in inches, required between
the bottom of a SWITCHBOARD and non -insulated busbars ?
,2|Page
A) 6
B) 8
C) 10
D) 12 - ANSWER-10 inches
table 408.5
Where liquid tight flexible metal conduit is installed outdoors
above grade, the interior of this raceway is considered to be a
____________ location
A) Dry
B) Wet
C) Damp
D) Raintight - ANSWER-Wet
article 300.38
,3|Page
At an electrical control panel which has exposed live parts 0f 120
volts to ground , the depth of clear WORKING SPACE shall be at
least ____________ inches.
A) 30
B) 36
C) 42
D) 48 - ANSWER-36
table 110.26 (A) (1)
Given: Nonmetallic sheathed cable is installed in an 18 - cu. inch
nonmetallic device box which is 2 - 1/4 inches x 4 inches (single
gang) and has no internal clamps.
The cable shall be supported within at least __________ inches
from the box.
A) 6
, 4|Page
B) 8
C) 12
D) 36 - ANSWER-12
article 334.30 (C)
Conductors in cables that run through bores holes located less
than ___________ inches from the nearest edge shall be
protected with steel plates having not less than 1/16-inch
thickness.
A) 1
B) 1 1/4
C) 2
D) 2 1/2 - ANSWER-1 - 1/4
article 300.4 (A) (1)