ICC VAPOR RECOVERY VT EXAM 2025/2026 NEWEST
ACTUAL EXAM WITH COMPLETE QUESTIONS AND
VERIFIED ANSWERS |ALREADY GRADED A+|
Automatic line leak detectors shall be installed on underground
pressurized piping and be capable to detect a 3-gallon per hour
leak rate at 10 psi within 1 hour, with a probability of detection of
at least ___? - ANSWER-95%
Stage II Vapor Recovery Systems are the transfer of vapors from
_________ to _________. - ANSWER-Vehicle Tank to UST
Who is ultimately responsible at a (GDF) Gasoline Dispensing
Facility? - ANSWER-Owner/ Operator
You are conducting a maintenance repair and you have a
gasoline spill, you shall take the following step as a safety
precaution. - ANSWER-Call 911-barricade spill area-clean as
much as you can and dispose of properly
, Page |2
Pressure Decay Test is tested in the of the UST - ANSWER-
Ullage
The Phil-tite riser float shall have __of clearance when installed -
ANSWER-13 inches
Upgrade requirements for UST's, spill and overfill prevention and
underground piping were required to be completed by what date?
- ANSWER-December 22, 1998
A balanced system shall contain a nozzle equipped with a ______
- ANSWER-Bellows
On a Vacuum assist inverted coaxial hose, the vapors travel: -
ANSWER-In the inside pathway of the hose
The tank riser drop tube is typically installed: - ANSWER-Below
the spill bucket
, Page |3
A ball float prevention system is designed and installed to: -
ANSWER-Alert the transfer operator when the tank is 90% full by
restricting flow
A UST will NOT require overfill prevention equipment if: -
ANSWER-Transfers are less than 25 gallons at a time
Suction piping operates at what pressure? - ANSWER-Less that
atmospheric pressure
close as practical to the suction pump, The maximum number of
check valves allowed for a system that operates at less than
atmospheric pressure shall be _ . - ANSWER-Below grade
Spill containers shall be a minimum capacity of _____ -
ANSWER-5 gallons
Design & Construction requirements for New Underground
Storage Tanks and all other components became effective. -
ANSWER-January 1 1995