When a device is inaccessible due to excessive height, such as
an atrium, what it the maximum interval for testing? ......
ANSWER ....... 18 months
When installing a wall-mounted fire telephone appliance to
the public, what is the acceptable maximum mounting height
from the floor? ...... ANSWER ....... 66 inches
Elevator lobby smoke detectors shall be mounted within a
maximum of which distance from the center-line of the door?
...... ANSWER ....... 21 feet
At minimum, when working near power lines with voltage of
600 volts and lower, an aerial lift operator shall maintain
,2|Page
which distance from the lines? ...... ANSWER ....... 10
feet
The use of unprotected EMT shall be permitted under which
conditions? ...... ANSWER ....... when in direct contact
with the earth
According to NFPA 70, what is the maximum unsupported
length of 1/2-inch flexible metallic conduit where flexibility
is required after installation? ...... ANSWER ....... 4 1/2
feet
What is the maximum bend (in degrees) permitted in a
conduit run between outlet boxes? ...... ANSWER .......
360 Degrees
If the primary power is disconnected and the fire alarm
system goes into an alarm condition, what is the minimum
acceptable time for secondary power to operate the voice
evacuation systems? ...... ANSWER ....... 15 minutes
A riser room temperature switch should activate when the
temperature falls below which level? ...... ANSWER .......
40 degrees F
,3|Page
According to NFPA 72, what is the maximum sound
pressure level permitted in a space with notification
appliances? ...... ANSWER ....... 110 dBA
What is the minimum interval for testing a single-station
smoke detector in multifamily units? ...... ANSWER .......
Annually
Where should a technician install a detector in relation to
beam that is less than 12 inches deep and less that 8 feet in
center? ...... ANSWER ....... At the bottom of the beam
An existing fire alarm cable in a drop ceiling will be spliced.
which one of the following splice locations will comply with
NFPA 70? ...... ANSWER ....... secured inside a listed
box or enclosure
Which function shall be tested for each newly installed
smoke detector? ...... ANSWER ....... smoke entry?
An 180 foot long corridor is 10 feet wide, with a smooth 10
foot ceiling, interrupted by 4-inch beams spaced every 10
, 4|Page
feet. How many heat detectors with a listed 30 foot spacing
are required? ...... ANSWER ....... 6 heat detectors
At which height must cables be physically protected when
being installed within an exposed ceiling? ...... ANSWER
....... 7 feet
When shall smoke detectors be installed during the
construction process? ...... ANSWER ....... After the
final cleanup of all trades
Where structural members are provided, intermediate metal
conduit shall be secured within which maximum distance
from an outlet box" ...... ANSWER ....... 3 feet
The requirement forbidding fire alarm circuits from being T-
tapped, unless indicated by the manufacturer's instructions, is
intended to prevent which type of improper malfunction?
...... ANSWER ....... monitoring integrity of installation
conductors?
What is the maximum operating temperature of TW
insulation? ...... ANSWER ....... 140 Degrees F, Table
310.15 (B)(16)