2000 cfm ...... ANSWER ....... The International
Mechanical Code requires a duct smoke detector in the
return for units over ________ cfm
15000 ...... ANSWER ....... The International
Mechanical Code (IMC) requires a duct smoke detector in
the supply for units over __________ cfm
4 hours ...... ANSWER ....... Digital alarm
communicator transmitters (DACT) which use call
forwarding to the DACR shall be tested with what
frequency?
600v ...... ANSWER ....... NPLFA cables shall be
insulated to __________ v
,2|Page
300v ...... ANSWER ....... PLFA cables shall be
insulated to _______ v
d ...... ANSWER ....... For sprinkler systems what type
of signal is a fire pump running?
a. alarm
b. supervisory
c. trouble
d. A and B
AHJ ...... ANSWER ....... A positive alarm sequence
requires the approval of the ___________.
Semniannually ...... ANSWER ....... How often shall a
remote annunciator used at the main entrance of a low-rise
residential apartment building be inspected?
Normal ...... ANSWER ....... According to NFPA 72,
the off-normal signal of a tamper switch control valve used in
sprinkler piping that is required for pressure-actuated water
flow alarm switch, shall not be restored at any valve position
except _____________?
,3|Page
12 in; 8 ft ...... ANSWER ....... When installing a heat-
sensing fire detector on the bottom of a beam, the beam must
be less than _____________ inches in depth and
_____________ feet on center?
b ...... ANSWER ....... Where a door is released to
provide a 2-hour fire rating directly from the smoke detector,
the detector shall be ______________
a. mounted as close as possible to the door being released
b. listed for door releasing service
c. identified for door releasing service
d. of the photoelectric type only
d ...... ANSWER ....... According to NFPA, smoke
detectors installed in the ducts of HVAC systems shall
initiate:
a. alarm
b. supervisory
c. trouble
d. a or b
, 4|Page
d ...... ANSWER ....... According to the IBC, shop
drawings shall include:
a. floor plan that indicates the use of all rooms
b. annunciators
c. voltage drop calculations
d. all of the above
Master Control Unit ...... ANSWER ....... The location
of remotely located power supplies shall be identified at the
________________
lower; 24 in ...... ANSWER ....... Heat detectors will be
installed in an elevator hoistway to shut down power to the
elevator prior to sprinkler activation. The heat detectors need
to have a _______________ temp rating and shall be located
______________ in from the sprinkler head.
Group B ...... ANSWER ....... A local community
college is what type of occupancy classification?
Group E ...... ANSWER ....... What type of occupancy
group for a school below the 12th grade?