NICET LEVEL 2 EXAM / NICET LEVEL 2 EXAM PREPARATION/NICET
LEVEL 2 EXAM PRACTICE EXAM WITH QUESTIONS AND CORRECT
ANSWERS| BRAND NEW VERSION!
During an inspection, you notice in rack sprinklers with material storage within 18
inches of the deflector, what action shall be taken?
A. the material shall be relocated more than 12 inches from the deflector
B. the material shall be relocated more than 18 inches from the deflector
C. The material shall be relocated more than 36 inches from the deflector
D. no action is required
D. no action is required
A Class _____ standpipe system provides 2 1/2 inch hose connections to supply
water for use by fire department
I
Consider an electrically supervised control valve. A distinctive signal shall indicate
movement from the valve's normal position during the first _____ revolutions of
the handwheel or when the stem of the valve has moved 1/5 of the distance from
its normal position?
2
Class II standpipe system demand shall include ____ GPM for the most remote
standpipe connection?
100
OSHA defines a(n) _______ as an individual stationed outside, one or more permit
spaces, who assesses the status of authorized entrants?
Attendant
Clearance from the top of storage to sprinkler deflectors shall be ____ or greater
where rubber tires are stored?
1|Page
, NICET Level 2 Exam / NICET Level 2 Exam Preparation
36 inches
The head available available from a water supply shall be figured based on a flow
of ____ percent of the rated capacity of the fire pump
150
When provided, the hydraulic design information sign for standpipe systems shall
be inspected?
Annually
A control valve supervisory signaling device shall be inspected ____?
Quarterly
An inspection of a hydrant house reveals that it is inaccessible. What type of
deficiency is this?
Impairment
Monitor nozzles shall be inspected with what frequency?
Semi annually
When flow testing hydrants, pitot readings of less than ___ psi, and more than
_____ psi, shall be avoided if possible?
10, 30
Mainline strainers shall be inspected and cleaned after each system flow
exceeding that of a nominal _____ inch orifice
2
Which of the following is a step in conducting a partial flow trip test?
A. partially open the main drain
B. fully open the auxiliary drain
C. Partially open the auxiliary drain
D. fully open the main drain
D. fully open the main drain
2|Page
, NICET Level 2 Exam / NICET Level 2 Exam Preparation
Before an employee enters a combined space, the internal atmosphere shall be
tested for _____?
A. oxygen
B. flammable gases
C. Flammable vapors
D. all of the above
D. all of the above
What is the inspection frequency for standpipe and hose system piping?
Annually
Hose houses shall be inspected with what frequency?
Quarterly
A sprinkler is loaded with a coating of dust. Which of the following is an
appropriate method of cleaning the sprinkler?
A. compressed air (without touching sprinkler)
B. vacuum with soft bristle brush used on sprinkler
C. Either A or B
D. none of the above, the sprinkler shall be replaced
A. compressed air (without touching sprinkler)
A corroded mainline strainer on a private service fire main would be classified as
a(n) _______?
Critical deficiency
Fire pump suction and discharge piping shall be hydrostatically tested at not less
than 200 psi pressure or at _____ psi in excess of the maximum pressure to be
maintained in the system, whichever is greater?
50
3|Page
, NICET Level 2 Exam / NICET Level 2 Exam Preparation
A control valve switch shall be tested by operating valve and verify signal receipt
to be within the first two revolutions of the handwheel or within _____ of the
travel distance, or per the manufacturer's published instructions?
One-fifth
Where replacing residential sprinklers manufactured prior to 2003 that are no
longer available from the manufacturer and are installed using a design density
less than 0.05 gpm/ft2, a residential sprinkler with an equivalent K-factor (+/-
______ percent) shall be permitted to be used provided the currently listed
coverage area for the replacement sprinkler is not exceeded.
5
CONSIDER A STANDPIPE AND HOSE SYSTEM WITH A HYDRAULIC DESIGN
INFORMATION SIGN. WHEN INSPECTING THE INFORMATION SIGN, WHERE
SHOULD IT BE LOCATED FOR AUTOMATIC AND SEMI AUTOMATIC SYSTEMS?
Secured to the water supply control valves
Dry barrel and wall hydrants shall be inspected ______ and after each operation?
Annually
Which of the following would be considered noncritical deficiency? (Select 3)
A. A hose rack that only swings out of the cabinet 120 degrees
B. A hose/hydrant house not fully equipped
C. A hose on standpipe that is not connected
D. A hose connection on a pressure reducing valve with a missing cap
B. A hose/hydrant house not fully equipped
C. A hose on standpipe that is not connected
D. A hose connection on a pressure reducing valve with a missing cap
When inspecting a diesel fire pump, the fuel tank shall be at least ______ full?
Two thirds