Stationary Engineer local 99 Exam Test Questions And Answers Verified 100% Correct The surface blowdown on a steam boiler is located ____________________ A. at the lowest visible part of the gauge glass B. on the mud drum C. at the highest part of the steam and waterdrum D. at the NOWL - ANSWER D. at the NOWL Bituminous coal has a ____________________________ content. A. high volatile B. high hydrogen C. high fixed carbon D. high ash - ANSWER A. high volatile Antracite coal has a ____________________________ content. A. high volatile B. high hydrogen C. high fixed carbon D. high ash - ANSWER C. high fixed carbon vaporstat control is sensitive to ___. A. pressure B. temperature C. electricity D. infrared rays - ANSWER A. pressure The air switch attached to the housing of a fully automatic rotary cup burner becomes operative where there is ___________________ A. low oil pressure B. fan failure C. excess primary air D. excess secondary air - ANSWER B. fan failure An automatic nonreturn valve is used with a(n) ___________________ A. engine B. pump C. boiler D. condenser - ANSWER C. boiler According to the ASME code, if a boiler has a MAWP that exceeds 100 psi the boiler must have __________________ blowdown vales A. 0 B. 1 C. 2 D. 3 - ANSWER C. 2 Boiler waterwalls should be blown down ________________. A. daily B. weekly C. when the firebox is cool but the boiler still has pressure D. every six months - ANSWER C. when the firebox is cool but the boiler still has pressure With all of the safety valves popping, the boiler pressure should not go higher than _____________________. A. 1 1/2 times the MAWP B. 6% above the MAWP C. 8% above theta set pressure D. 10% above the set pressure - ANSWER B. 6% above the MAWP When making a hydrostatic test on a boiler, the pressure is___________ A. 2 times the safety valve setting B. 1 1/2 times the MAWP C. 1 1/4 times the MAWP D. operating pressure plus atmospheric pressure - ANSWER B. 1 1/2 times the MAWP At a water temperature of 212 F, one boiler horsepower is equivalent to the evaporation _____________ pounds of water per hour A. 34.5 B. 62.5 C. 180 D. 970.3 - ANSWER A. 34.5 A(n) ______________________ test is used to test the relieving capacity of a safety valve. A. hydorstatic B. accumulation C. Orsat analysis D. Ringelmann - ANSWER B. accumulation While replacing a broken gauge with the boiler under pressure, the water level is checked by _________________ A. blowing down the water column B. giving the boiler a bottom bow C. using try cocks D. using air cocks - ANSWER C. using try cocks Safety valves are located on the uppermost part of the steam and water drum and the outlet of the superheater header. True False - ANSWER True A desuperheater is only used in low pressure steam plants. True False - ANSWER False An economizer is a heat exchanger that absorbs heat from the gases of combustion leaving the boiler. True False - ANSWER True Superheating steam is impossible at low steam pressure True False - ANSWER False Three methods of heat transfer are radiation, convection, and conduction. True False - ANSWER True The forced and induced draft fans on a boiler are the same size and operate at the same speed. True False - ANSWER False Purging a furnace before firing can prevent a furnace explosion True False - ANSWER True The atmospheric pressure at sea level will support a column of mercury approximately 30' high. True False - ANSWER True

Meer zien Lees minder
Instelling
Stationary Engineer Local
Vak
Stationary Engineer local

Voorbeeld van de inhoud

Stationary Engineer local 99 Exam Test
Questions And Answers Verified 100%
Correct

The surface blowdown on a steam boiler is located ____________________
A. at the lowest visible part of the gauge glass
B. on the mud drum
C. at the highest part of the steam and waterdrum
D. at the NOWL - ANSWER D. at the NOWL

Bituminous coal has a ____________________________ content.
A. high volatile
B. high hydrogen
C. high fixed carbon
D. high ash - ANSWER A. high volatile

Antracite coal has a ____________________________ content.
A. high volatile
B. high hydrogen
C. high fixed carbon
D. high ash - ANSWER C. high fixed carbon

vaporstat control is sensitive to ___.
A. pressure
B. temperature
C. electricity
D. infrared rays - ANSWER A. pressure

The air switch attached to the housing of a fully automatic rotary cup burner becomes
operative where there is ___________________
A. low oil pressure
B. fan failure
C. excess primary air
D. excess secondary air - ANSWER B. fan failure

An automatic nonreturn valve is used with a(n) ___________________
A. engine
B. pump

,C. boiler
D. condenser - ANSWER C. boiler

According to the ASME code, if a boiler has a MAWP that exceeds 100 psi the boiler
must have __________________ blowdown vales
A. 0
B. 1
C. 2
D. 3 - ANSWER C. 2

Boiler waterwalls should be blown down ________________.
A. daily
B. weekly
C. when the firebox is cool but the boiler still has pressure
D. every six months - ANSWER C. when the firebox is cool but the boiler still has
pressure

With all of the safety valves popping, the boiler pressure should not go higher than
_____________________.
A. 1 1/2 times the MAWP
B. 6% above the MAWP
C. 8% above theta set pressure
D. 10% above the set pressure - ANSWER B. 6% above the MAWP

When making a hydrostatic test on a boiler, the pressure is___________
A. 2 times the safety valve setting
B. 1 1/2 times the MAWP
C. 1 1/4 times the MAWP
D. operating pressure plus atmospheric pressure - ANSWER B. 1 1/2 times the MAWP

At a water temperature of 212 F, one boiler horsepower is equivalent to the evaporation
_____________ pounds of water per hour
A. 34.5
B. 62.5
C. 180
D. 970.3 - ANSWER A. 34.5

A(n) ______________________ test is used to test the relieving capacity of a safety
valve. A. hydorstatic
B. accumulation
C. Orsat analysis
D. Ringelmann - ANSWER B. accumulation

,While replacing a broken gauge with the boiler under pressure, the water level is
checked by _________________ A. blowing down the water column
B. giving the boiler a bottom bow
C. using try cocks
D. using air cocks - ANSWER C. using try cocks

Safety valves are located on the uppermost part of the steam and water drum and the
outlet of the superheater header.
True
False - ANSWER True

A desuperheater is only used in low pressure steam plants.
True
False - ANSWER False

An economizer is a heat exchanger that absorbs heat from the gases of combustion
leaving the boiler.
True
False - ANSWER True

Superheating steam is impossible at low steam pressure
True
False - ANSWER False

Three methods of heat transfer are radiation, convection, and conduction.
True
False - ANSWER True

The forced and induced draft fans on a boiler are the same size and operate at the
same speed.
True
False - ANSWER False

Purging a furnace before firing can prevent a furnace explosion
True
False - ANSWER True

The atmospheric pressure at sea level will support a column of mercury approximately
30' high.
True
False - ANSWER True

, Boiler drum safety valves must open before the superheater safety valve to ensure a
back flow.
True
False - ANSWER False

A calorimeter measures excess air being used for combustion
True
False - ANSWER False

The main function of a continuous blowdown system is to lower the total concentration
of solids in the boiler.
True
False - ANSWER True

In a natural draft system, the lowest draft reading is obtained at the furnace.
True
False - ANSWER False

The main function of a steam trap is to remove air and condensate without the loss of
steam.
True
False - ANSWER True

One of the purposes of a bottom blowdown line is remove impurities from the boiler
True
False - ANSWER True

A slow-opening valve requires ______________ complete turns to be fully opened or
closed.
A. 3
B. 5
C. 7
D. 9 - ANSWER B. 5

High pressure boilers equipped with quick-opening and screw-type valves are blown
down by opening the __________ valve first and closing it _____________.
A. quick-opening, first
B. screw-type, last
C. quick-type, last
D. quick-opening valves are never used on high pressure - ANSWER C. Quick-type,
last

Geschreven voor

Instelling
Stationary Engineer local
Vak
Stationary Engineer local

Documentinformatie

Geüpload op
14 oktober 2025
Aantal pagina's
31
Geschreven in
2025/2026
Type
Tentamen (uitwerkingen)
Bevat
Vragen en antwoorden

Onderwerpen

$13.99
Krijg toegang tot het volledige document:

Verkeerd document? Gratis ruilen Binnen 14 dagen na aankoop en voor het downloaden kun je een ander document kiezen. Je kunt het bedrag gewoon opnieuw besteden.
Geschreven door studenten die geslaagd zijn
Direct beschikbaar na je betaling
Online lezen of als PDF

Maak kennis met de verkoper

Seller avatar
De reputatie van een verkoper is gebaseerd op het aantal documenten dat iemand tegen betaling verkocht heeft en de beoordelingen die voor die items ontvangen zijn. Er zijn drie niveau’s te onderscheiden: brons, zilver en goud. Hoe beter de reputatie, hoe meer de kwaliteit van zijn of haar werk te vertrouwen is.
TopGradeGuru Teachme2-tutor
Volgen Je moet ingelogd zijn om studenten of vakken te kunnen volgen
Verkocht
15
Lid sinds
1 jaar
Aantal volgers
0
Documenten
2399
Laatst verkocht
1 maand geleden
GRADEHUB

We provide access to a wide range of professionally curated exams for students and educators. It offers high-quality, up-to-date assessment materials tailored to various subjects and academic levels. With instant downloads and affordable pricing, it\'s the go-to resource for exam preparation and academic success.

1.5

2 beoordelingen

5
0
4
0
3
0
2
1
1
1

Recent door jou bekeken

Waarom studenten kiezen voor Stuvia

Gemaakt door medestudenten, geverifieerd door reviews

Kwaliteit die je kunt vertrouwen: geschreven door studenten die slaagden en beoordeeld door anderen die dit document gebruikten.

Niet tevreden? Kies een ander document

Geen zorgen! Je kunt voor hetzelfde geld direct een ander document kiezen dat beter past bij wat je zoekt.

Betaal zoals je wilt, start meteen met leren

Geen abonnement, geen verplichtingen. Betaal zoals je gewend bent via iDeal of creditcard en download je PDF-document meteen.

Student with book image

“Gekocht, gedownload en geslaagd. Zo makkelijk kan het dus zijn.”

Alisha Student

Bezig met je bronvermelding?

Maak nauwkeurige citaten in APA, MLA en Harvard met onze gratis bronnengenerator.

Bezig met je bronvermelding?

Veelgestelde vragen