NEWEST EXAM 2025-2026 | COMPLETE
QUESTIONS AND CORRECT ANSWERS | GRADED
A+ | LATEST EXAM | VERIFIED ANSWERS
Terms in this set (99)
The RV on a RP drips You have a leaking check valve #2 under a
steadily while the backpressure condition
customer is not using
water. You close the
shutoff valve #2 and the
dripping stops. What does
that indicate?
The RV on a RP drips You have a leaking check valve #1
steadily while the
customer is not using
water. You close the
shutoff valve #2 and the
dripping does not stop.
You then open test cock
#4 to induce flow across
the device and the
dripping lets up or stops.
What does that indicate?
, The RV on a RP drips You most likely have an issue with the relief valve. It
steadily while the could potentially be an issue with both check valve #1
customer is not using and the relief valve
water. You close the
shutoff valve #2 and the
dripping does not stop.
You then open test cock
#4 to induce flow across
the device and the
dripping does not stop.
What does that indicate?
The RV on a RP drips The RV leaks and/or the diaphragm is damaged
steadily while the
customer is using water.
What does this indicate?
Check valve #1 on a DC 1.0 PSID
assembly must hold a
minimum PSID of _____
Check valve #2 on a DC 1.0 PSID
assembly must hold a
minimum PSID of _____
The maximum allowed 10 PSI
pressure drop across a DC
assembly according to
AWWA is _____
When testing for the PSID Leaking shut off valve #1
across check valve #1 on a
DC assembly, the sight
tube on test cock #3 does
not stop flowing. What
does that indicate?