Which two Factors that affect Fire Alarm Systems
performance, are mostly determined on the jobsite?
A-Equipment and System Design
B-Inspections and Maintenance
C-Installation and Maintenance
D-Installation and Equipment - . . ANSWER ✔ ✔C-
Installation and Maintenance
What type of indication would appear at the Fire Alarm
Control Panel when a short circuit is introduced on a IDC?
A-No Indication
B-A Trouble Signal
C-A Supervisory Signal
D-An Alarm Signal - . . ANSWER ✔ ✔D-An Alarm Signal
,2|Page
What are the most common operating principals for Spot
Type Smoke Detector? - . . ANSWER ✔ ✔Ionizing and
Photoelectric
What are the most common operating principals for Spot
Type Heat Detectors? - . . ANSWER ✔ ✔Rate of Rise and
Fixed
Class "B" IDC and NAC circuits can be identified by a
certain wiring requirements, what are they? - . . ANSWER
✔ ✔E.O.L (end of line resistor) and one pair of wires
Class "A" IDC and NAC circuits can be identified by a
certain wiring requirement, what is it? - . . ANSWER ✔
✔A complete loop made of a pair leaving the FACP and a
pair returning to the FACP
How much time is allowed for a troubled signal to activate
on the FACP once the trouble has been introduced on a
monitored device or circuit?
A- 10 Secs
B- 90 Secs
,3|Page
C- 200 Secs
D- 240 Secs - . . ANSWER ✔ ✔C- 200 Secs
A supervisory signal appearing at the FACP indicated what
condition has occurred in the system? - . . ANSWER ✔ ✔A
Fire Suppression device has been placed in an Off Normal
Position.
What are the 3 basic types of Fire Alarm Circuits in use
today? - . . ANSWER ✔ ✔1. Initiating Device Circuit (IDC)
2. Notification Appliance Circuit (NAC)
3. Signaling Line Circuit (SLC)
What is the minimum number of adequate power supplies
required for a Protect Premises or Local Alarm System
Control Panel?
A- One
B- Two
C- The number required is dependent on the size of the
FACP
D- There is no requirement specified - . . ANSWER ✔ ✔B-
Two
, 4|Page
Can a Signaling Line Circuit arrange for a Class "B"
operation be "T" tapped? If so, under what conditions?
A- Yes, under all conditions
B- No, under all conditions
C- It is dependent on the system configuration
D- Only when wired in a Fail Safe circuit arrangement - . .
ANSWER ✔ ✔A- Yes, under all conditions
As Ceiling height increases, what effect does it have on the
spacing requirements of Spot Type Smoke Detector and
Heat Detectors?
A- Reduces sensitivity, requires additional detectors
B- Increases sensitivity, requires additional detectors
C- Reduces sensitivity, requires fewer detectors
D- Increases sensitivity, requires fewer detectors - . .
ANSWER ✔ ✔A- Reduces sensitivity, requires additional
detectors
Loss of power to the primary power supply for a FACP will
result in what type of signal at the Fire Alarm Control
Panel?