COMPLETE SET QUESTIONS WITH 100% RATED
CORRECT ANSWERS | GRADE A+(2025)
Terms in this set (104)
Who is responsible for the The Property owner or designated representative
inspection, testing, maintenance
and impairment of a water based
fire protection system?
Who's responsibility is it to The property owner or designated representative
provide
accessibility to components
of a water based fire
protection system?
Who shall correct or repair The property owner or designated representative
deficiencies or impairments
found during the inspection,
test and maintenance required
by
standard?
Who is qualified to preform the Qualified maintenance personal or a qualified contractor
corrections and repairs of a
water based fire protection
system?
A permanently marked metal or An Information Sign,
rigid
plastic information sign shall be
placed at the system control
riser supplying an
antifreeze loop, dry system,
preaction, or auxiliary system
control valve?
Records made during all The Authority Having Jurisdiction
inspections, tests and
, maintenance shall be made
available to who upon request?
All records shall be maintained The Property Owner
by?
How long should subsequent 1 year,
records be retained?
After the testing and Shall be restored to full operational condition,
reinstallation of plugs and caps
for auxiliary drain and test
valves, what action is
required?
To avoid false alarms where a conducting any test or procedure that could result in the activation of an
supervisory service is provided alarm,
the alarm receiving facility
shall be notified by the
property owner or designated
representative
before?
Sprinklers shall be inspected Shall be inspected from the floor level annually
when and how?
Sprinklers shall not show leakage; shall be free of corrosion, foreign materials, paint, and
signs of the following? physical damage; and shall be installed in the correct
orientation
Sprinklers installed installed in Shall not require inspection,
concealed spaces such as above
ceilings shall what?
Sprinklers installed in areas that During each scheduled shutdown
are
inaccessible for safety
considerations due to process
operations shall be inspected?
The supply of spare sprinklers Annually,
shall be inspected when?
A spare sprinkler wrench shall Every type of sprinkler,
be required for what?