Terms in this set (249)
When is the initial pressure test After blowdown of a distribution piping
conducted, by a medical gas
installer, on a nitrous oxide
system?
In those portions of systems Polymeric
intended to handle oxygen at
pressures greater than 350 psi
the interconnecting hose shall
NOT contain materials?
In a Category 1 Dental and Gas Color coding & non-standard pressure
Vacuum Piping system, which of
the following is an NFPA 99
requirement for the labeling of
pipes?
Which of the following Cut ends shall be rolled smooth or deburred
treatments shall be performed
before brazing cut ends of a
tube to be installed in a medical
gas piping system?
Manifolds for gas cylinders Local, master
shall actuate a(an) signal
and shall activate an
indicator at all__alarm panels to
indicate when or just before
changeover from one header to
the other.
In a non-anesthetizing area, on Station outlet/inlet
which side of a zone valve shall
the pressure/vacuum sensor
,be located?
, What is the purpose of using an Assure that all ambient air has been removed from the pipeline
oxygen analyzer during the
piping purge prior to brazing?
A medical gas master or area Audible and visual
alarm panel shall be set to
actuate a(an)
____________________
indicator
when the communication with an
alarm- initiating device is
disconnected.
When an EOSC becomes the Providing four connection points to both master alarms
temporary supply source, a
facility will monitor the system
by use of which of the
following?
Which of the following installation by anyone other than 6010 certified personnel is NOT
conditions must be met where permitted
medical gas and vacuum
systems are installed by non-
certified personnel?
Which of the following Medical air compressor supply sources
systems shall NOT be
permitted to be located in an
outdoor enclosure?
Metallic flexible joints are being suitable for service at 150 psig or above
used in the pipeline for vibration
control. Which of the following is
NOT required of such joints?
who shall witness the installer- the authority having jurisdiction, or its designee
performed standing vacuum
test?
the medical air compressor 25 feet
intake shall be located a
minimum of how many feet from
any exhaust or plumbing