1. A fire pump was installed in a low-rise residential building with a required fire
alarm system. What are the requirements for the pump running signal?
a. It shall be a supervisory signal.
b. It shall be an alarm signal.
c. It shall be a supervisory or alarm signal.
d. A pump running signal is not required. - ANSWER c
2. A licensed electrician was hired to install duct detectors mounted on the air
ducts of a 5,000 CFM unit. Which of the follwoing statements is true?
a. The smoke detector must be listed for use in air ducts
b. The detectors can initiate a supervisory signal
c. The detectors can initiate an alarm signal
d. All of the above - ANSWER d
3. Record drawings, as-builts, shall contain approval documetnation resulting
from any _______________?
,a. variances
b. performance-based designs
c. risk analysis
d. all of the above - ANSWER d
4. A smoke detector must not be installed in elevator hoistways except if_______.
A. the elevator machine room is at the top of the hoistway
B. the hoistway is less than 30' in length
C. the hoistway has sprinkler coverage
D. installed to activate elevator hoistway smoke relief equipment
E. B & D are correct
F. C & D are correct - ANSWER F
5. Exposed optical fibers must be supported by the_______. - ANSWER
Building Structure
6. A smoke detector must be marked with their nominal production_______and
tolerance. - ANSWER Sensitivity
7. Consider a fire alarm system in a Use Group A. According to the IBC, activating
the fire alarm in a Use Group A occupancy with an occupant load of _____ or
more shall initiate a signal using an emergency voice/alarm communication
system? - ANSWER 1000
,8. Which of the following is true for automatic drift compensation of detectors?
A. The FACP must identify the affected detector when the compensation limit is
surpassed by the detector.
B. The affected detector must show the limit has been reached at the detector.
C. This feature is only allowed for household systems.
A & B - ANSWER A
9. Alarm signals must not be lost, interrupted, or delayed by more
than______when primary power failure occurs. - ANSWER 10 seconds
10. What is the maximum time allowed between the activation of an initiating
device in alarm condition, to the time the alarm condition is displayed and
recorded at the supervising station? - ANSWER 90 seconds
11. In both exposed and concealed areas, where a cable is installed through bored
holes in the joists, rafters, or wood members; holes must be drilled so that the
edge of the hole is no closer than____from the nearest edge. - ANSWER 1
1/4"
12. Capable of being reached for operation, renewal, and inspection is known as
what?
A. accessible (regarding equipment)
B. accessible (regarding wiring methods)
C. accessible (regarding termination)
D. accessible (regarding FACP) - ANSWER A
, 13. After acceptance testing, what type of drawings are required to be presented
to the building owner?
A. As Built Drawings
B. Contract Drawings
C. Point-To-Point Diagrams
D. Manufacturer's Drawings - ANSWER A
14. According to the IBC, strobe lights/appliances shall not be required in
________________ ? - ANSWER Elevator Cars
15. According to the IBC, which of the following fire alarm systems are required in
a Group F occupancy?
A. a manual and automatic fire alarm system with occupant notification.
B. an automatic fire alarm system without occupant notification
C. a manual fire alarm system without occupant notification.
D. a manual fire alarm system with occupant notification - ANSWER D
16. Conductors of shunt circuits shall not be smaller than ______________ and
shall be ____________.
A. 14 AWG / Insulated
B. 18 AWG / Insulated
C. 14 AWG / Covered
D. 18 AWG / Covered - ANSWER 14 AWG