Where do you record the ratings of the btu/hr input for a
customers current appliances? .....Answer.......Customer gas
appliance use profile form
_____________ is used to determine the amount of propane
required to operate appliances at a reduced demand, and
assumes full cycle happen typically, and don't operate
simultaneously. .....Answer.......Effective system load
,age 2 of 34
Most critical issues when selecting a container:
.....Answer.......Customer's propane demand, above or
underground, and vaporization.
When a container is sized for vapor service, the goal is to
ensure the _________________ is higher than the demand of
propane. .....Answer.......Vaporization rate
when selecting/sizing a tank, it's important to consider if it will
be ________________ or ______________.
.....Answer.......Above ground, underground
For underground tanks, it's important to consider __________
and ______________ .....Answer.......Soil temperature, frost
penetration
When sizing a container, it is important to consider the most lite
conditions the container will operate in. T/F? .....Answer.......False
,age 3 of 34
When determining container size, the temperature used for tank
sizing should be the lowest temperature anticipated. T/F?
.....Answer.......True
NFPA 58 states all containers installed/filled at a customers
home must be ___ ft in any direction from combustibles.
.....Answer.......10
NFPA 58 states all containers installed/filled at a customers
home must be ___ ft in any direction from an above ground
tank/ flammable liquid. .....Answer.......20
NFPA 58 states all containers filled on site must be positioned so
the fill connection, relief valve, and liquid level gauge vent are
___ ft from sources of ignition. .....Answer.......10
, age 4 of 34
For DOT cylinders, 500+ gallons of total water capacity on a
customers property must be ___ ft or further from building.
.....Answer.......25
Above ground tanks with less than 125g water capacity may be
placed next to a building and must be ___ ft away from any
discharge. .....Answer.......5
_________________ are the most common method used to join
steel and wrought iron pipes in residential/small commercial
installs. .....Answer.......Threaded fittings
Acceptable types of fittings include: .....Answer.......Steel,
malleable iron, ductile iron, press-connect
____________ can be joined using manufacturer prescribed
procedures like heat fusion, or mechanical fittings.
.....Answer.......Polyethylene (PE) pipe