ICC VAPOR RECOVERY – VT EXAM QUESTIONS
AND ANSWERS 2025
Type of sealant you should you use on a Phil-Tite Ball
Float nipple: - .....ANSWER ...✔✔ Pipe dope
Number of open valves on the clean air separator: -
.....ANSWER ...✔✔ One
You must be CERTIFIED by Healy to re-connect a Healy
breakaway, True or False? - .....ANSWER ...✔✔ False
The type of pressure gauge is recommended to test
Healy Vac - .....ANSWER ...✔✔ SYSA gauge
measuring 0-100 WC
On new construction, after July 1, 2004, Can you install
an in-ground Spill Bucket? - .....ANSWER ...✔✔ YES-
When Piping is monitored and with VAC
,2|Page
According to Executive Order 201 - Healy P/V Valve
should be torqued at - .....ANSWER ...✔✔ 20-50 ft-
lbs
For a fire to burn, these (3) three primary elements
must exist: - .....ANSWER ...✔✔ Fuel, Oxygen,
Ignition Source
When working with Electrical - Lock Out Tag Out
procedures are under these guidelines. - .....ANSWER
...✔✔ CAL-OSHA
Organization that certifies vapor recovery systems. -
.....ANSWER ...✔✔ CARB or ARB
According to RP 500, a level II technician may NOT
inspect this part. - .....ANSWER ...✔✔ Replace VP
1000 Healy Pump
where hanging hardware repairs must be tracked. -
.....ANSWER ...✔✔ GDF maintenance log
,3|Page
approved sealant when assembling a Phil-Tite Drop
Tube. - .....ANSWER ...✔✔ JB-Kwik
Material direct bury OPW container sleeve shall be
made of. - .....ANSWER ...✔✔ Stainless steel
What P/V vent cap shall be tightened to. - .....ANSWER
...✔✔ 20-50 ft lbs
From dispenser to manifold - 2" diameter vapor piping
( 2" ID) and From manifold to tank - 3" diameter vapor
piping (3" ID) - .....ANSWER ...✔✔ Vapor piping
What is the maximum run for vapor piping? -
.....ANSWER ...✔✔ No maximum run
How you know a nozzle spout is bad. - .....ANSWER
...✔✔ 'BAD O-rinqs
, 4|Page
According to PEI RP 300, on a balance Stage II vapor
recovery system nozzle, Vapors typically flow in what
direction of the coaxial hose? - .....ANSWER ...✔✔
The outside pathway
What is the maximum allowable number of P/V caps
allowed on a UST fuel system? - .....ANSWER ...✔✔
One
On a Healy Air Separator, there are four Ball Valves, the
following shall be observed? - .....ANSWER ...✔✔
One valve shall remain open on top
The Pressure settings for the UST Vent Cap is. -
.....ANSWER ...✔✔ .0+- 0.5inches H2O Negative
Pressure 1,0+-2.0 inches H2O Positive Pressure
Given that in a balance Stage II vapor recovery system,
the nozzle is equipped with a flexible nozzle bellows
that seals around the automobile fill pipe. This is how
vapors will typically flow. - .....ANSWER ...✔✔ From