Test pressure gauges shall be capable of being read
within ___% of test pressure - .....ANSWER ...✔✔ 90-
110
Pressure gauges used on test equipment shall be
calibrated at least - .....ANSWER ...✔✔ Semi-
annually
The temp used for drying hydro equipment shall not
exceed _________ degrees inside the shell -
.....ANSWER ...✔✔ 150 degrees
The equipment for hydrostatic testing of high pressure
cylinders and cartridges (dot 3series) shall meet the
specifications of - .....ANSWER ...✔✔ Methods of
hydrostatic testing of compressed gas cylinders
, 2|Page
A hydrostatic test pump, hand or power operated shall
be capable of producing not less than __________ of
the test pressure and shall include appropriate check
valves and fittings - .....ANSWER ...✔✔ 150 percent
Dry chemical, stored pressure, with mild steel shells,
brazed brass shells, or aluminum shells - .....ANSWER
...✔✔ Hydro every 12 years
Dry chemical, stored pressure, cartridge or cylinder
operated with mild steel shells need to be inspected how
often?? - .....ANSWER ...✔✔ 12 yr intervals
everything else is 5yr
How often do dry chemicals with stainless steel shells
need to be inspected - .....ANSWER ...✔✔ Every 5
years
If, at any time, a fire extinguisher shows evidence of
___________________________ to the extent as to
indicate weakness, it shall be condemned or hydrostati-
cally retested - .....ANSWER ...✔✔ dents,
mechanical injury,