Qualification for S98 certificate of fitness include all except - Answers Must be 21 years of age
If you fail the written test you will not be permitted to Retest for - Answers 90 days
The following is an example of what type of Ceiling - Answers Stooped
A bean is defined as a structural or non structural solid member which could jacks down into
the rooms base more than _____ and is located more than _____ apart on center - Answers Down
more than4" and 3' apart
The following are examples of line type detection except - Answers ionization smoke detector
He could tonight a circuit to which automatic or manual initiating devices are connected where
the signal received does not identify the device operated is called? - Answers A signaling line
circuit
Secondary power supplies are required to have sufficient power to operate the fire alarm
system in a non alarm condition for _______ hours and then be capable of operating all
notification devices for a minimum of ______ minutes - Answers 24 hours and 5 minutes
Secondary power supplies for emergency voice evacuation systems are required to have
sufficient power to operate the system in a non along condition for ______ hours and kin be
capable of operating the system during a fire or other emergency for a minimum of ______
minutes - Answers 24 hours and 15 minutes under maximum load
Secondary power supply shall automatically provide power to the protected premises fire alarm
system within _______ seconds when ever primary power fails to provide minimum voltage
required for proper operation? - Answers 10 seconds
Cording to NFPA chapter 4, batteries shall be permanently marked with what information? -
Answers Month and year of manufacture
NFPA 72 "record of completion" is prepared: - Answers upon completion of installation at just
acceptance test
According to NFPA chapter 4, the control panel charging apparatus shall be taken full of
recharging batteries within _____ _____ after batteries have been fully discharged? - Answers 24
hours
According to the fire code of New York City, smoke detectors may be tested by the following
methods except for: - Answers Measured aerosol smoke introduced into the detector
What type of drawing typically shows correct conductor counts? - Answers Riser diagrams
According to the fire code and fire rules, who is responsible for preventing unnecessary and
, unwanted alarms? - Answers Owner of a promise or a part thereof
I'll take you way and which according to NFPA chapter 4, a coded alarm signal shall consist of
not less than ______ complete rounds of the number transmitted. Each round shall consist of not
less than a ______ impulses - Answers 3 rounds and 3 impulses
According to the fire rules, who is responsible for making in trees in the smoke detector
maintenance log? - Answers The fire safety director or a person designated by building owners
if no FSD
According to NFPA chapter 4, installation Conductors shall be monitored for integrity. The
occurrence of a single open or single ground fault condition shall be automatically indicated
within ______ seconds - Answers 200 seconds
All of the following are good conductors of electricity except - Answers carbon
Which of the following is an example of an initiating device? - Answers Supervisory air pressure
switch and photo electric smoke detector
Into voice along and initiating device which is destroyed as a result of its operation is what type?
- Answers Non restorable
It's the face of the nobleman equipment you shall be designed so that it is capable of
performing its intended function at ______ of its name plate voltage - Answers 85%
When installing heat detectors on ceilings, a row detector shall be located - Answers Within 3' of
the peak
The minimum distance for mounting of a spot type smoke detector from an air supply diffuser
is? - Answers 3' from diffusers
This is regarding manual fire alarm boxes, NFPA 72 requires that they be conspicuous,
unobstructed, and ________ - Answers accessible
Regarding manual fire alarm boxes, NFPA 72 requires that travel distance to the nearest fire
alarm Box shall not exceed - Answers 100 feet
The maximum number of water flow switches permitted to be connected to a single IDC shall
not exceed - Answers 5
Fire pumps shall be supervised for: (find the incorrect answer) - Answers Pump running -
supervisory signal
to meet the requirements for distinctive signals, building evacuation signals shall be? - Answers
ANSI 53.41 Temporal 3 signal
A listed relay used to initiate fire safety functions shall be located within ________ _______ of the