The hydrostatic test interval for a dry chemical extinguisher with a
stainless steel shell is every __ years
Ans: 5
The hydrostatic test interval for a stored-pressure water, water mist,
loaded stream, and/or antifreeze is __ years
Ans: 5
The hydrostatic test interval for a Wetting agent extinguisher is __
years.
Ans: 5
The Hydrostatic test interval for a AFFF (aqueous film-forming foam)
extinguisher is __ years.
Ans: 5
The Hydrostatic test interval for a FFFP (film-forming fluoroprotein
foam) extinguisher is __ years.
All rights reserved © 2025/ 2026 |
, Page |2
Ans: 5
The hydrostatic test interval for a Carbon Dioxide extinguisher is __
years.
Ans: 5
The hydrostatic test interval for a Wet Chemical extinguisher is __
years.
Ans: 5
The hydrostatic test interval for a Dry chemical, stored-pressure, with
mild steel shells, brazed brass shells, or aluminum shells is __ years.
Ans: 12
The hydrostatic test interval for a Dry chemical, cartridge- or cylinder-
operated, with mild steel shells is __ years.
Ans: 12
The hydrostatic test interval for a Halogenated Agent extinguisher is
__ years.
Ans: 12
All rights reserved © 2025/ 2026 |
, Page |3
The hydrostatic test interval for a Dry powder, stored-pressure,
cartridge- or cylinder- operated, with mild steel shells extinguisher is __
years.
Ans: 12
The maintenance internal examination for a stored-pressure loaded
stream and antifreeze is __ years.
Ans: 1
The maintenance internal examination for a Pump tank water and
pump tank, calcium chloride based extinguisher is __ years.
Ans: 1
The maintenance internal examination for a dry chemical, cartridge-
and cylinder- operated, with mild steel shells extinguisher is __ years.
Ans: 1
The maintenance internal examination for a Dry powder, cartridge-
and cylinder- operated, with mild steel shells extinguisher is __ years.
Ans: 1